33
Field wiring
7.4 Connecting to a 3G4010CF Interface Device outside Canada
For information on Compatible Receivers see 12.0 Appendix A: Compatible Receivers on
page 94.
A typical connection is shown in Figure 23. The 3G4010CF is powered separately from the
PCS-100 and requires 2 DSC RM-2 relays (sold separately). The PCS-100 Passive
Communications Interface Board (sold separately) is also required.
Figure 23 Connecting an FACP to a 3G4010CF Interface Device outside Canada
Note:
The DSC interface device 3G4010 is required if the installation requires ULC
S559 certification. The DSC interface device 3G4010CF is required if the
installation requires UL864 9th edition certification.
Telephone
Line A
Connection
EOL
Line 2
C.O.
Line 1
C.O.
PCS-100
P
OW
E
R
2
4
V
G
N
D
P
G
M4
G
N
D
1
4
V
NC
C
O
M
N
O
T
B
L
R
E
L
AY
J
W
1
AUX SUPPLY
+
-
+
-
To GSM/GPRS
Internet
Computer
Printer
SUR-GARD
SYSTEM IV
Internal IP : X.X.X.X
External IP : X.X.X.X
SG-Systems
Console 2.1
Default Gateway : X.X.X.X
Sub-Net Mask:X.X.X.X
Port #: YYYY (UDP)
Router
Conventional
input configured
as 3G4010CF
radio trouble
FA-300
3G4010CF
TRBL
ALARM
RELAY
SPV
RELAY
TRBL
RELAY
NO
C
NO
C
NO
C
+
-
FA-300 - 3G4010CF Connection - Typical Diagram
Typical Installation outside Canada
- All units must be installed in the same room
- All extended wiring must be in metallic conduit
- Wiring between FACP and 3G4010CF: 20 feet max.
- Contact DSC to reprogram the zone inputs to match the
FACP as shown in this diagram
- Use 2 DSC RM-2 Relays (sold separately) to supervise
both AC failure trouble and low battery trouble
- Install the DSC RM-2 Relays inside the 3G4010CF
enclosure above the PS4086
3G4010CF
TRBL
PGM4
COM
Z3
Z2
Z1
T
1
R
1
NC COM NO
DSC
RM-2
Relay
EOL
-
PS4086
Transformer
Battery
DC IN
+12V COM
AC IN
+
ACT LBT
NC COM NO
DSC
RM-2
Relay
EOL
-
+
BAT+ BAT-
3G4010CF
3G4010CF
TRBL
+
-
+
-
Conventional
input configured
as AC failure
trouble
Conventional
input configured
as low battery
trouble