MIOX RIO Series Operators Manual
P/N: 102-00076-G
Page 25
Plumbing Connections Required for Startup
All water and brine systems are compatible with schedule 80 PVC. MIOX strongly
recommends schedule 80 CPVC for all mixed-oxidant or sodium hypochlorite solutions and
hydrogen venting. Where possible, all connections should be solvent weld rather than
threaded to prevent the possibility of leaks. All piping should be supported at 3 - 4 ft. (1 m)
intervals. Isolation valves should be included on all inlet lines external to the RIO Series
OSG.
Feed Water Connection
Feed water requirements for the RIO Series OSG are given in Table 8. Additional feed water
is based on water softener requirements. Consult water softener specifications for required
flow rates. A minimum of 35 psi (242 kPa) feed water pressure at the OSG is required to
ensure stable flow and a continuous supply of 5-25 psi (34-172 kPa) brine feed to the
electrolytic cell. To protect against low water pressure, an auto adjusting flow control valve is
included in the piping manifold to compensate for inconsistent flow and pressure fluctuations.
It uses a turbine flow sensor that sends pulses to the PLC when the turbine is spinning.
Based on the rate of the pulses, the system can calculate the feed water flow rate and adjust
the flow control valve accordingly. This setting is critical for proper oxidant production, cell
cooling, and other key operating parameters. A liquid filled pressure gauge is included in the
plumbing compartment to visually monitor the cell pressure (Figure 14). Maximum supply
pressure to the RIO Series OSG should not exceed 100 psi (689 kPa). For supply pressure
above 100 psi (689 kPa), a pressure regulator must be added to lower the pressure to a
range of 35-100 psi (242-689 kPa).
Table 8 Feed Water Requirements
Cell Module
GPH
GPM
LPH
M1
75
1.25
283.5
M2
150
2.50
567.0
M3
225
3.75
850.5
M4
300
5.00
1134.0
M5
375
6.25
1417.5
H1
75
1.25
283.5
H2
150
2.50
567.0
H3
225
3.75
850.5
H4
300
5.00
1134.0
H5
375
6.25
1417.5