15
Installation
Field output
The field output is for shunt wound motors only. Do not
make any connections to F1 and F2 when using a
permanent magnet motor.
Use 18 AWG wire to connect the field output to a shunt
wound motor. Table 1 lists the field output connections.
Table 1. Field Output Connections
Line Voltage
Approximate
Connect Motor
(VAC)
Field Voltage (VDC)
Field To
115
50
F1 and L1
115
100
F1 and F2
230
100
F1 and L1
230
200
F1 and F2