21
Warning
The inhibit circuit is used for frequent starts and stops. It
must never be used as an emergency stop. It may not stop a
drive that is malfunctioning. Removing AC line power (both L1
and L2) is the only acceptable method for emergency
stopping.
Minarik strongly recommends the installation of
a STOP/START switch for emergency stopping.
Inhibit circuit (MM21051C ONLY)
Maintaining a connection between the inhibit pins causes the motor
to coast to zero speed. Removing the connection between the
inhibit pins allows the motor to accelerate to the speed set by the
speed adjust potentiometer (Figure 10).
Figure 10. Inhibit Circuit Connections (MM21051C only)
Operation
Содержание MM21051C
Страница 9: ...3 Figure 2 MM21151C Dimensions ALL DIMENSIONS IN INCHES MM Dimensions...
Страница 10: ...4 Dimensions Figure 3 MM21251C Dimensions ALL DIMENSIONS IN INCHES MM...
Страница 11: ...5 Figure 4 MM21151C and MM21251C Back View Cased Mounting Keyhole Locations...
Страница 31: ...25 Figure 12 Dynamic Braking Circuit Connection Operation...
Страница 33: ...27 Calibration Figure 13 Calibration Trimpot Layouts MM21051C MM21151C MM21251C...
Страница 37: ...31 Figure 14 Typical TORQUE and IR COMP Settings actual settings may vary with each application Calibration...
Страница 50: ...44 Figure 23 MM21051C MM21151C and MM21251C block diagram Block Diagrams...
Страница 51: ...45 Figure 24 MM21151C switching circuit connections...
Страница 52: ...46 Block Diagrams Figure 25 MM21251C switching circuit connections...
Страница 54: ...48 Notes...