6
Installation
Warning
Under no circumstances should power and logic leads be
bundled together. Induced voltage can cause
unpredictable behavior in any electronic device, including
motor controls.
As a general rule, Minarik recommends shielding of all
conductors.
If it is not practical to shield power conductors, Minarik
recommends shielding all logic-level leads. If shielding logic
leads is not practical, the user should twist all logic leads with
themselves to minimize induced noise.
It may be necessary to earth ground the shielded cable. If noise
is produced by devices other than the drive, ground the shield
at the drive end. If noise is generated by a device on the drive,
ground the shield at the end away from the drive. Do not
ground both ends of the shield.
If the drive continues to pick up noise after grounding the
shield, it may be necessary to add AC line filtering devices, or
to mount the drive in a less noisy environment.
Shielding guidelines