Gas and Air Adjustments
PELLERIN MILNOR CORPORATION
1. Connect the high side of the manometer to
test point 1
(
). Leave the other side open
to the atmosphere.
2. Open
the
manual test valve
fully (R,
3. Adjust
the
main gas regulator
(W,
) to value shown in
2.9.
Step 6: Setting Burner Minimum Fire
Display or Action
Explanation
u
This mode sets the
modulating gas valve
to 000 and displays
the inlet temperature (Fahrenheit shown).
SETUP MODE E 079F
MIN FIRE ROD GAS SW
1. Calculate the desired minimum fire temperature using data from
2. Slowly adjust the
Y minimum adjustment
on top of the
modulating gas valve
(T,
and
). Turn adjustment CCW to increase the temperature or CW to decrease
temperature, until value calculated from data in
display. After making an adjustment, wait for the dryer display to settle.
2.10.
Step 7: Setting High Gas Pressure Switch
1. Attach one side of manometer (high pressure side of differential pressure gauge) to
test point
3
(
); leave the other side open to atmosphere.
2. Set
the
high gas pressure switch
dial (K,
3. Start with the
manual test valve
fully open. Close this valve slowly until value shown in
is read on manometer.
4. Verify that when the set value is reached, the
$
light blinks, the switch trips, and the burner
extinguishes.
5. Open
the
manual test valve
fully.
2.11.
Step 8: Setting Low Gas Pressure Switch
1. Connect one side of manometer (high pressure side of differential pressure gauge) to
test
point 1
(
); leave the other side open to atmosphere.
2. Start with the
external gas shut-off valve
open. Close this valve slowly until value shown in
is read on manometer.
3. Slowly rotate the
low gas pressure switch dial
(L,
) until the
#
status light is
on
.
Open the
external gas shut-off valve
fully.
4. Slowly close the external gas shut-off valve and verify that when the value is reached, the
#
slatus light blinks, the switch trips and the burner extinguishes.
5. Open the external gas shut-off valve fully.
2.12.
Step 9: Setting the Burner Pressure Switch
1. Put dryer in Setup Mode E, (see "Step 6: Setting Burner Minimum Fire.")
2. Attach the low pressure side of the manometer to the plenum air gauge point (item 2,
) and leave the other side open to the atmosphere.
69
Содержание 7272TG1L
Страница 6: ......
Страница 8: ...2 ...
Страница 46: ...40 ...
Страница 47: ...Section 1 Service and Maintenance 41 ...
Страница 103: ...Section 2 Drive Assemblies 97 ...
Страница 131: ...Section 3 Gas Assemblies 125 ...
Страница 148: ...142 ...
Страница 149: ...Section 4 Steam Assemblies 143 ...
Страница 155: ...Section 5 Pneumatics 149 ...
Страница 166: ...160 ...
Страница 167: ...Section 6 Door Assemblies 161 ...
Страница 176: ...170 ...
Страница 177: ...Section 7 Water Assemblies 171 ...
Страница 182: ...176 ...
Страница 183: ...Section 8 Installation Drawings 177 ...
Страница 184: ...178 ...
Страница 185: ...179 ...
Страница 186: ...180 ...
Страница 187: ...181 ...
Страница 188: ...182 ...
Страница 189: ...183 ...
Страница 190: ...184 ...
Страница 191: ...185 ...
Страница 192: ...186 ...
Страница 193: ...187 ...
Страница 194: ...188 ...
Страница 195: ...189 ...
Страница 196: ...190 ...
Страница 197: ...191 ...
Страница 198: ...192 ...
Страница 199: ...193 ...
Страница 200: ...194 ...
Страница 201: ...195 ...
Страница 202: ...196 ...
Страница 203: ...197 ...
Страница 204: ...198 ...
Страница 205: ...199 ...
Страница 206: ...200 ...