Pellerin Milnor Corporation
Applicable Models (cont'd.)
Step
Gauge
Points
1
5050TG_
6450TG_
6458TG_, 6464TG_
7272TG_
Fireye
L+G
Fireye
L+G
Fireye
L+G
Fireye
L+G
8
Low gas pressure
GGL
2.25 (5.6)
2.25
(5.6)
3.25 (8)
3.25 (8)
3.25 (8)
3.25 (8)
2.75 (6.8)
2.75 (6.8)
9
Burner box
pressure
GAB
0.06
(0.15)
0.04 (1)
0.06 (0.15)
0.06
(0.15)
0.06
(0.15)
0.06
(0.15)
0.06
(0.15)
0.06
(0.15)
10
Back pressure
n. a.
0.8 (2)
0.8 (2)
0.8 (2)
0.8 (2)
0.8 (2)
0.8 (2)
0.8 (2)
0.8 (2)
1. The reference point is atmosphere unless two values are shown for the gauge point.
2. Must not exceed. A pressure that exceeds the maximum can damage the regulator.
Set the Heating System—Air Heat Dryer