5-10. Electrical Service Guide
Elec Serv 2011
−
08
NOTICE
−
INCORRECT INPUT POWER can damage this welding power source. This welding power source requires a CONTINUOUS supply of
input power at rated frequency
(+
10%) and voltage
(+
10%). Phase to ground voltage shall not 10% of rated input voltage. Do not use a genera-
tor with automatic idle device (that idles engine when no load is sensed) to supply input power to this welding power source.
NOTICE
−
Actual input voltage should not be 10% less than minimum and/or 10% more than maximum input voltages listed in table. If actual input
voltage is outside this range, output may not be available.
Failure to follow these electrical service guide recommendations could create an electric shock or fire hazard. These recommenda-
tions are for a dedicated circuit sized for the rated output and duty cycle of the welding power source.
In dedicated circuit installations, the National Electrical Code (NEC) allows the receptacle or conductor rating to be less than the rating
of the circuit protection device. All components of the circuit must be physically compatible. See NEC articles 210.21, 630.11, and
630.12.
60 Hz Three-Phase
Input Voltage (V)
230
460
575
Input Amperes (A) At Rated Output
43.9
26.6
22.4
Max Recommended Standard Fuse Rating In Amperes
1
Time-Delay Fuses
2
50
30
25
Normal Operating Fuses
3
70
40
35
Min Input Conductor Size In AWG
4
8
10
10
Max Recommended Input Conductor Length In Feet (Meters)
122
(37)
311
(95)
481
(147)
Min Grounding Conductor Size In AWG
4
8
10
10
Reference: 2011 National Electrical Code (NEC) (including article 630)
1 If a circuit breaker is used in place of a fuse, choose a circuit breaker with time-current curves comparable to the recommended fuse.
2 “Time-Delay” fuses are UL class “RK5” . See UL 248.
3 “Normal Operating” (general purpose - no intentional delay) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” ( 65 amp and
above).
4 Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table
310.15(B)(16). If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable
requirements.
Содержание PipeWorx 400
Страница 14: ...OM 236 891 Page 10...
Страница 90: ...OM 236 891 Page 86 SECTION 8 ELECTRICAL DIAGRAMS Figure 6 1 Circuit Diagram For Welding Power Source...
Страница 91: ...OM 236 891 Page 87 254 310 B...
Страница 92: ...OM 236 891 Page 88 Figure 6 2 Circuit Diagram For Single Or Dual Wire Feeder...
Страница 93: ...OM 236 891 Page 89 236 220 E...
Страница 94: ...OM 236 891 Page 90 Figure 6 3 Circuit Diagram For Cooler 238 662 B...
Страница 95: ...OM 236 891 Page 91 Figure 6 4 Flow Diagram For Cooler Pump Filter Radiator Flow Indicator Tank Torch...