OM-252 624 Page 27
!
Always ground generator frame to
vehicle frame to prevent electric
shock and static electricity hazards.
!
Also see AWS Safety & Health Fact
Sheet No. 29, Grounding of Portable
And Vehicle Mounted Welding Gen-
erators.
!
Bed liners, shipping skids, and
some running gear insulate the
welding generator from the vehicle
frame. Always connect a ground
wire from the generator equipment
grounding terminal to bare metal on
the vehicle frame as shown.
!
Use GFCI protection when operat-
ing auxiliary equipment. If unit does
not have GFCI receptacles, use
GFCI-protected extension cord. Do
not use GFCI receptacles to power
life support equipment.
1
Equipment Grounding Terminal (On
Front Panel)
2
Grounding Cable (Not Supplied)
3
Metal Vehicle Frame
Connect cable from equipment ground
terminal to metal vehicle frame. Use #8
AWG or larger insulated copper wire.
Electrically bond generator frame to ve-
hicle frame by metal-to-metal contact.
5-4. Grounding Generator To Truck Or Trailer Frame
rot_grnd2 2012
−
03
−
800 652-D
1
3
2
GND/PE
5-5. Installing Exhaust Pipe
1/2 in.
Tools Needed:
Exhaust1 2008
−
01 Ref. 803 604 / Ref. 215 664
!
Stop engine and let cool.
Point exhaust pipe in desired di-
rection but always away from front
panel and direction of travel.
Содержание big blue 700 duo pro
Страница 51: ...OM 252 624 Page 47 6 8 Fuel Hour Gauge Descriptions...
Страница 66: ...OM 252 624 Page 62 SECTION 9 ELECTRICAL DIAGRAMS Figure 9 1 Circuit Diagram For Export Welding Generator...
Страница 67: ...OM 252 624 Page 63 250 340 E...
Страница 68: ...OM 252 624 Page 64 Figure 9 2 Circuit Diagram For North American Welding Generator...
Страница 69: ...OM 252 624 Page 65 249 603 D...