OM-228 874 Page 23
4-15. Connecting 3-Phase Input Power (Continued)
!
Turn Off welding power source, and
check voltage on input capacitors
according to Section 8-3 before
proceeding.
!
Installation must meet all National and
Local Codes
−
have only qualified per-
sons make this installation.
!
Disconnect and lockout/tagout input
power before connecting input
conductors from unit. Follow estab-
lished procedures regarding the in-
stallation and removal of lockout/
tagout devices.
!
Make input power connections to the
welding power source first.
!
Always connect green or
green/yellow conductor to supply
grounding terminal first, and never to
a line terminal.
.
The Auto-Line circuitry in this unit
automatically links the power source to the
primary voltage being applied. Check input
voltage available at site. This unit can be
connected to any input power between 208
and 575 VAC without relinking the power
source.
See rating label on unit and check input
voltage available at site.
1
Input Power Conductors (Customer
Supplied Cord)
Select size and length of conductors using
Section 4-14. Conductors must comply with
national, state, and local electrical codes. If
applicable, use lugs of proper amperage
capacity and correct hole size.
Welding Power Source Input Power
Connections
2
Strain Relief
Install strain relief of proper size for unit and
input conductors. Route conductors (cord)
through strain relief and tighten screws.
3
Welding Power Source Grounding
Terminal
4
Green Or Green/Yellow Grounding
Conductor
Route green or green/yellow grounding
conductor through current transducer and
connect to welding power source grounding
terminal first.
5
Welding Power Source Line Terminals
6
Input Conductors L1 (U), L2 (V) And L3
(W)
Connect input conductors L1 (U), L2 (V) and
L3 (W) to welding power source line
terminals.
Reinstall side panel onto welding power source.
Disconnect Device Input Power
Connections
7
Disconnect Device (switch shown in
the OFF position)
8
Disconnect Device (Supply) Grounding
Terminal
9
Disconnect Device Line Terminals
Connect green or green/yellow grounding
conductor to disconnect device grounding
terminal first.
Connect input conductors L1 (U), L2 (V), and
L3 (W) to disconnect device line terminals.
10 Overcurrent Protection
Select type and size of overcurrent protection
using Section 4-14 (fused disconnect switch
shown).
Close and secure door on line disconnect de-
vice. Follow established lockout/tagout pro-
cedures to put unit in service.
Input5 2012
−
05
Notes
Work like a Pro!
Pros weld and cut
safely. Read the
safety rules at
the beginning
of this manual.
Содержание Auto-Axcess 300 DI
Страница 14: ...OM 228 874 Page 10...
Страница 25: ...OM 228 874 Page 21 Notes...
Страница 48: ...OM 228 874 Page 44 Figure 9 2 Circuit Diagram For Welding Power Source Part 2 Of 2...
Страница 49: ...OM 228 874 Page 45 228 875 F Part 2 Of 2...
Страница 50: ...OM 228 874 Page 46 Ref 219 267 B Figure 9 3 Circuit Diagram For Peripheral Motor Interface...
Страница 51: ...OM 228 874 Page 47 Notes...