OM-350 Page 15
2-15. Positioning Jumper Links
ssb5.1 2/92 – ST-800 337-B
Y
Disconnect and lockout/tag-
out input power before plac-
ing or moving jumper links.
Jumper links allow operation on dif-
ferent input voltages and are facto-
ry set for the highest input voltage.
Check input voltage available at
site.
Remove side panel to check jump-
er links.
1
Input Voltage Label – Only
One Is On Unit
Look at jumper links and compare
link position with unit label.
2
Input Voltage Jumper Links
Move links to match input voltage.
For example, use 230 volts position
when 230 volts input power is avail-
able.
Reinstall side panel or go on to Sec-
tion 2-17.
1
Tools Needed:
S-048 604-A
S-081 896-A
2
1/2 in
3/8 in
2-16. Electrical Service Guide
Input Voltage
200
230
460
575
Input Amperes At Rated Output
206
180
90
72
Max Recommended Standard Fuse Or Circuit
Breaker Rating In Amperes
300
250
125
110
Min Input Conductor Size In AWG/Kcmil
2/0
1/0
4
6
Max Recommended Input Conductor Length
In Feet (Meters)
139 (42)
163 (50)
318 (97)
336 (102)
Min Grounding Conductor Size In AWG/Kcmil
4
4
6
6
Reference: 1993 National Electrical Code (NEC).
S-0092J