OM-229 253 Page 26
4-14. Electrical Service Guide
Elec Serv 2009
−
08
A. 1000 Ampere Rated Welding Output
Failure to follow these electrical service guide recommendations could create an electric shock or fire hazard. These recommenda-
tions are for a dedicated branch circuit sized for the rated output and duty cycle of the welding power source.
60 Hz
Input Voltage (V)
230
460
575
Input Amperes (A) At Rated Output
180
90
72
Max Recommended Standard Fuse Rating In Amperes
1
Time-Delay Fuses
2
225
110
90
Normal Operating Fuses
3
250
125
110
Min Input Conductor Size In AWG
4
3/0
3
4
Max Recommended Input Conductor Length In Feet (Meters)
204
(62)
337 (103)
438 (134)
Min Grounding Conductor Size In AWG
4
4
6
6
Reference: 2008 National Electrical Code (NEC) (including article 630)
1 If a circuit breaker is used in place of a fuse, choose a circuit breaker with time-current curves comparable to the recommended fuse.
2 “Time-Delay” fuses are UL class “RK5” . See UL 248.
3 “Normal Operating” (general purpose - no intentional delay) fuses are UL class “K5” (up to and including 60 amps), and UL class “H” ( 65 amps and
above).
4 Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table
310.16. If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable requirements.
B. 1000 Ampere Rated Welding Output
Failure to follow these electrical service guide recommendations could create an electric shock or fire hazard. These recommenda-
tions are for a dedicated branch circuit sized for the rated output and duty cycle of the welding power source.
50 Hz
Input Voltage (V)
380
400
440
Input Amperes (A) At Rated Output
111
105
96
Max Recommended Standard Fuse Rating In Amperes
1
Time-Delay Fuses
2
125
125
110
Normal Operating Fuses
3
175
150
150
Min Input Conductor Size In AWG
4
2
2
3
Max Recommended Input Conductor Length In Feet (Meters)
322
(98)
357
(109)
358
(109)
Min Grounding Conductor Size In AWG
4
6
6
6
Reference: 2008 National Electrical Code (NEC) (including article 630)
1 If a circuit breaker is used in place of a fuse, choose a circuit breaker with time-current curves comparable to the recommended fuse.
2 “Time-Delay” fuses are UL class “RK5” . See UL 248.
3 “Normal Operating” (general purpose - no intentional delay) fuses are UL class “K5” (up to and including 60 amps), and UL class “H” ( 65 amps and
above).
4 Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table
310.16. If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable requirements.