
.
A complete Parts List is available at www.MillerWelds.com
OM-242 880 Page 18
4-12. Extension Cord Data
.
When calculating max. cord length, remember to include conductor length from line disconnect device to input power receptacle.
Input Voltage
Input Power
Phase
Hertz
Fuse Size Or
Circuit Breaker Rating
Conductor Size
Max. Cord Length
208 V
1
50/60
Time-Delay
2
5
0 A
Normal Operating
3
70 A
10 AWG
55 ft (17 m)
230 V
1
50/60
Time-Delay
2
50 A
Normal Operating
3
60 A
10 AWG
67 ft (21 m)
208 V
3
50/60
Time-Delay
2
30 A
Normal Operating
3
40 A
12 AWG
68 ft (21 m)
230 V
3
50/60
Time-Delay
2
3
0 A
Normal Operating
3
35 A
12 AWG
83 ft (25 m)
380 V
3
50/60
Time-Delay
2
15 A
Normal Operating
3
20 A
14 AWG
148 ft (45 m)
460 V
3
50/60
Time-Delay
2
15 A
Normal Operating
3
20 A
14 AWG
216 ft (66 m)
575 V
3
50/60
Time-Delay
2
10 A
Normal Operating
3
15 A
14 AWG
341 ft (104 m)
2 “Time-Delay” fuses are UL class “RK5” .
3 “Normal Operating” (general purpose
−
no intentional delay) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” ( 65 amp and
above).
Notes
Содержание CE-60T
Страница 51: ...OM 242 880 Page 47 Notes ...
Страница 52: ...OM 242 880 Page 48 SECTION 8 ELECTRICAL DIAGRAM Figure 8 1 Circuit Diagram ...
Страница 53: ...OM 242 880 Page 49 243 018 C ...
Страница 57: ...Notes ...
Страница 58: ...Notes ...