Table 17 LCD ‘Non Flashing’- burner off
Status Display messages ‘Non Flashing’ with the burner off
MAXIMUM WATER TEMP
The boiler water temperature has reached
the set point
FAN OFF-ON
The fan has switched off. Unit will try to reset
automatically.
FAN TOO LOW
Detected fan speed to low. Unit will try to
reset automatically.
Check wiring terminals on top of transformer
FLAME IDENTIFICATION
Flame detected. . Unit will try to reset
automatically.
BLEED
Boiler going through automatic venting cycle
33. Fault Finding
.
Fault Indicator (flashing display)
To a certain extent the boiler will attempt to automatically overcome some of the faults
that occur.
For example, it will attempt 4 ignition sequences before going to lock out.
In situations where it has not been successful, the boiler will lock out and can only be re-
started by pressing the manual (Red) reset button.
When in lock out mode, the error is displayed in the LCD display as a flashing message.
The following list indicates the messages shown and the descriptions of the faults. The
numbers shown in the left hand column, suggest the possible cause.
By using the numbered lists attached, the cause of the fault can be quickly identified and
a repair effected.
Table 18 Fault Display Flashing
Display message
FLASHING
Type of fault
Check table
row number
STB- supply
Maximum flow temperature
has been reached
2,4,5,21,23,24,29,30
STB- fluegas
Maximum flue gas
temperature has been
reached
4,5,23,24,29,33
Fanspd high
Fan speed is too high
7,8,9,39,40
Fanspd low
Fan speed is too low
7,8,9,39,40
Ignit fault
No flame after 4 attempts
10,11,16,18,22,25
No flame
Flame failed during
operation
11,12,16,22,25,2632,44
False flame
False flame detection
18,35
S1 disconnect
Sensor or cable interrupted
3,41,42,43
S3 disconnect
Sensor or cable interrupted
3,41,42,43
S4 disconnect
Sensor or cable interrupted
3,41,42,43
S7 disconnect
Sensor or cable interrupted
3,41,42,43
Program end
Sensor or cable interrupted
3,41,42,43
Gasvalve
No phase connection for
gas valve
34,20