44
CODE
DESCRIPTION
F10
Unsigned integer
High byte: month
Low byte: day
F11
Unsigned integer
High byte: hour (24 hour format)
Low byte: minute
F12
Unsigned integer – Date and time format for relay display only
High byte: Date format, 0=DD/MM/YYYY, 1=MM/DD/YYYY
Low byte: Time format, 0=12 hour, 1=24 hour
F13
Unsigned integer – Change Group by...
0=Change group by menu, 1=change group change by level of digital
input
F14
Unsigned integer
A scaled numeric value of certain units
Eg. 123 may represent 1.23A or 1.23s
Refer to individual resisger's 'Units and Scale' and 'range' for detail
F15
Unsigned integer – Cold Load Pick-up element
Bit 0 - 2: Reserved
Bit 3: tIo>
Bit 4: tIo>>
Bit 5: Reserved
F16
Unsigned integer – Input n reset option
(For input function set as reset)
Bit 0: 0= Not to reset trip/alarm, 1=to reset trip/alarm
Bit 1: 0= Not to reset thermal state, 1=to reset thermal state
F17
Unsigned integer – Input n Blocked element
(For input function set as blocking)
Bit 0 - 2: Reserved
Bit 3: tIo>
Bit 4: tIo>>
Bit 5: Reserved
F18
Unsigned integer – Relay n link element
Bit 0 - 2: Reserved
Bit 3: Io>
Bit 4: Io>>
Bit 5: Reserved
Bit 6: Aux 1
Bit 7 - 8: Reserved
Bit 9: Idemand
Bit 10: Remote trip
Содержание x20
Страница 1: ...user manual X20 EARTH FAULT RELAY...
Страница 2: ...2 EARTH FAULT RELAY Ver 1 00...
Страница 7: ...7 7 1 2 Dimension of X20 96mm 96mm 125mm 105mm Front View Side View...
Страница 12: ...12 2 3 Wiring With 3 phase 4 wires...
Страница 13: ...13 13 With 3 phase 3 wires...
Страница 45: ...45 45 Appendix A IDMT Curves Normal Inverse Appendix A...
Страница 46: ...46 Very Inverse...
Страница 47: ...47 47 Normal Inverse 1 3 10 1 0 0 9 0 8 0 7 0 6 0 5 0 4 0 3 0 2 0 1 0 05...
Страница 48: ...48 Long time Inverse...
Страница 49: ...49 49 Extremely Inverse...