Each Event or Alarm Record consists of 6 words:
Word Number
Description
Format
Units and scale Range
1
Year
F7
year
0 - 199 (as 2000 - 2199)
2
month, day
F10
month,day
0 - 12, 0 - 31
3
hour, minute
F11
hour, minute
0 - 23, 0 - 59
4
Milliseconds
F7
ms
0 - 59999
5
Record code
See below
record code
6
Record value
See below
record value
Word number 5:
Word number 6:
Event and Alarm Record code
Event and Alarm Record value
0: None
If code is Setting change
1 - 6: Reserved
Value is the register address of setting being changed
7: Io> start
8: tIo>> trip
If code is Group change
9: Io>> start
0: group 1
10: tIo>> trip
1: group 2
11: Remote trip
12: Remote acknowledge
If code is output relay latching, output relay unlatching:
13: Remote reset
Bit 0: Output relay 1
14: Setting change
Bit 1: Output relay 2
15: Remote thermal state reset
16: Maintenance mode
If code is input activate, input deactivate:
17 - 19: Reserved
Bit 0: Input 1
20: Group change
21: tAux 1
22: Reserved
23 - 25: Reserved
26: tIo> reset
27: tIo>> reset
28: Relay latching
29: Relay unlatching
30: Input activate
31: Input deactivate
32: Idemand alarm
33: General starting
34: Cold load function starting
Содержание x20
Страница 1: ...user manual X20 EARTH FAULT RELAY...
Страница 2: ...2 EARTH FAULT RELAY Ver 1 00...
Страница 7: ...7 7 1 2 Dimension of X20 96mm 96mm 125mm 105mm Front View Side View...
Страница 12: ...12 2 3 Wiring With 3 phase 4 wires...
Страница 13: ...13 13 With 3 phase 3 wires...
Страница 45: ...45 45 Appendix A IDMT Curves Normal Inverse Appendix A...
Страница 46: ...46 Very Inverse...
Страница 47: ...47 47 Normal Inverse 1 3 10 1 0 0 9 0 8 0 7 0 6 0 5 0 4 0 3 0 2 0 1 0 05...
Страница 48: ...48 Long time Inverse...
Страница 49: ...49 49 Extremely Inverse...