*If user request to change setting, press Enter button.
4.3.5 Input Menu
LCD
Display
Description
Input 1 Func
Set the function of Input 1. Setting choices are
included None, Aux1, Reset, Blocking, Select
Group, Cold Load PU and Sync Clock.
Input 1 Type
Set how the input 1 is activated. For Active High,
a voltage to the input activates the input, For
Active Low, opening of the input activates the
input.
Aux 1 Type
Aux timer
Set the value for the time delay of Aux 1 definite
time.
Reset Type
Blocking Type
Block Io>?
Set to Yes to enable blocking of Io>
Block Io>>? Set to Yes to enable blocking of Io>
Aux 1
The input is used as auxiliary alarm or tripping signal.
If tAux is not assigned to trip output relay (whether it is
assigned to a start output relay or not), activation of the input
will generate an Aux Alarm signal after time delay.
If tAux is assigned to trip output relay, the input will generate
an Aux Trip signal after time delay.
Reset Type
Enable the input to reset trip
Содержание x20
Страница 1: ...user manual X20 EARTH FAULT RELAY...
Страница 2: ...2 EARTH FAULT RELAY Ver 1 00...
Страница 7: ...7 7 1 2 Dimension of X20 96mm 96mm 125mm 105mm Front View Side View...
Страница 12: ...12 2 3 Wiring With 3 phase 4 wires...
Страница 13: ...13 13 With 3 phase 3 wires...
Страница 45: ...45 45 Appendix A IDMT Curves Normal Inverse Appendix A...
Страница 46: ...46 Very Inverse...
Страница 47: ...47 47 Normal Inverse 1 3 10 1 0 0 9 0 8 0 7 0 6 0 5 0 4 0 3 0 2 0 1 0 05...
Страница 48: ...48 Long time Inverse...
Страница 49: ...49 49 Extremely Inverse...