6.5 Accuracy
Earth Fault Overcurrent Io> and Io>>
Measuring Range
0.02 to 10 x Ion
Accuracy of pickup current
±3% of set value or 20mA
whichever is greater
Accuracy of DFT time
±3% or 30ms whichever is
greater
Accuracy of IDMT time
±5% or 30ms whichever is
greater
6.6 Insulation Test
IEC60255-5 Insulation Test
High voltage dielectric
withstand test
2kV rms, 1 minute
High voltage impulse test
5kV, 1.2/50us
6.7 EMC Standard Test
IEC60255-26 standard Test
Electrical fast transient
IEC61000-4-4, Power Supply 4kV, 5 kHz
Electrical fast transient
IEC61000-4-4, other inputs
2kV, 5 kHz
Surge IEC6100-4-5,
4kV Common mode
IEC 60255-22-5
2kV Differential mode
Electrostatic discharge
IEC61000-4-2, air discharge
8kV