82
b.2 total harMonic Distortion calculation
Total Harmonic Distortion (THD) is a power quality indicator used to show the extent of voltage and
current waveform distortion by the load. The THD is calculated by the following equation:
THD={h
2
+h
3
+h
4
+........+h
32
}/ h
1
x100%
where h
n
represents the n
th
harmonic component of the quantity, resolved using Fourier’s Transform.
b.3 seQuence coMPonents calculation
Sequence components are abstract quantities resolved from the phase voltages and currents.
They describe the degree and nature of imbalance and phase reversal. Any 3-phase system can
be resolved into 3 balanced 3-phase components: positive, negative and zero sequences using the
following equations:
I
zero
=
1
⁄
3
{ I
1
+ I
2
+ I
3
}
I
pos
=
1
⁄
3
{ I
1
+ aI
2
+ a
2
I
3
}
I
neg
=
1
⁄
3
{ I
1
+ a
2
I
2
+ aI
3
}
V
zero
=
1
⁄
3
{ V
1
+ V
2
+ V
3
}
V
pos
=
1
⁄
3
{ V
1
+ aV
2
+ a
2
V
3
}
V
neg
=
1
⁄
3
{ V
1
+ a
2
V
2
+ aV
3
}
These values are useful for identifying sources of imbalance and for troubleshooting protective relay
settings and wiring faults such as phase reversals.
where a = 120˚ unit vector phase shifter
Appendix
B.2
B.3
Содержание DPM680
Страница 1: ......
Страница 71: ...71 Fig 83 Energy and Power webpage display Webpage Operations 4 2...
Страница 73: ...73 Fig 84 Energy and Power webpage display Webpage Operations 4 3...
Страница 78: ...78 Table A 1 Specification list Appendix A...
Страница 79: ...79 Table A 1 Specification list Appendix A...
Страница 80: ...80 Table A 1 Specification list Appendix A...
Страница 84: ......