15
To reset the energy register values, please see
section 3.7.5
The following parameters should also be
reviewed against the default value and modified
if necessary:
• demand interval and sub interval block for
thermal current demand, see section 3.4.4
• demand interval and sub interval block for
power demand, see section 3.6.5
The following registers should be reviewed and
reset if necessary:
• maximum and minimum phase voltages, see
sections 3.3.3 & 3.3.4
• maximum and minimum line voltages, see
sections 3.3.5 & 3.3.6
• maximum and minimum current, see sections
3.4.2 & 3.4.3
• maximum current demand, see section 3.4.5
• maximum and minimum inductive power factor,
see section 3.5.4
• maximum and minimum capacitive power factor,
see section 3.5.5
• maximum and minimum frequency, see section
3.5.6
• maximum power demand, see section 3.6.6
• maximum and minimum active power, see
sections 3.6.7 & 3.6.8
• maximum and minimum reactive power, see
sections 3.6.9 & 3.6.10
• maximum and minimum apparent power, see
sections 3.6.11 & 3.6.12
2.4
TCp/ip ConnECTion sETup
The meter runs on IPv4 and its TCP/IP settings
can either be fixed by the user or assigned
via DHCP. By default, the TCP/IP settings are
assigned via DHCP and the alternate default
fixed TCP/IP settings are as follow:
IPv4 address: 192.168.28.28
Subnet mask: 255.255.255.0
Gateway address: 192.168.28.1
These values can be changed at the meter as
explained in section 3.8.2.1.
Installation
2.3
2.4
Содержание DPM680
Страница 1: ......
Страница 71: ...71 Fig 83 Energy and Power webpage display Webpage Operations 4 2...
Страница 73: ...73 Fig 84 Energy and Power webpage display Webpage Operations 4 3...
Страница 78: ...78 Table A 1 Specification list Appendix A...
Страница 79: ...79 Table A 1 Specification list Appendix A...
Страница 80: ...80 Table A 1 Specification list Appendix A...
Страница 84: ......