The terminal block provides convenient wire connection for external device control and tests. All contacts are dry, rated low voltage/low
current, so DO NOT APPLY 120VAC to any of these contacts.
Attach your wiring to the terminal block and push it up into the terminal block receptacle of the DA-700.
•
1 = +24DC
+24VDC Power Source to Operate Accessories
•
2 = Gnd
Ground or -24VDC or -12VDC
•
3 = Zone 1
Common for Zone 1 Relay (RL-1 LED)
•
4 = Zone 1
Normally Open Contact for Zone 1
•
5 = Zone 2
Common for Zone 2 Relay (RL-2 LED)
•
6 = Zone 2
Normally Open Contact for Zone 2
•
7 = Zone 3
Common for Zone 3 Relay (RL-3 LED)
•
8 = Zone 3
Normally Open Contact for Zone 3
•
9 = Timer Relay
Normally Closed Contact for Timer Relay (RL-4 LED)
•
10 = Timer Relay
Common for Timer
•
11 = Timer Relay
Normally Open Contact for Timer Relay
•
12 = All Detect Relay Normally Closed Contact for All-Detection Relay (RL-5 LED)
•
13 = All Detect Relay Common for All Detection Relay
•
14 = All Detect Relay Normally Open Contact for All-Detection Relay
•
15 = Mute/Delay
Accessory Switch Input for Mute/Delay Control if green internal Mute/Delay button is not convenient
•
16 = Mute/Delay
Accessory Switch Input for Mute/Delay Control if green internal Mute/Delay button is not convenient
•
17 = Gnd
Ground or -24VDC or -12VDC
•
18 = +12DC
+12VDC Power Source to Operate Accessories
•
19 = Not Used
Terminal not currently assigned/used
•
20 = Low Battery
Logic Levels: +10 Volts means the Battery is okay, 0 Volts means the Battery is low and the D19 LED is on
NOTE: If any relay operates (the relay’s LED is on) the contacts between the Common and Normallly Open will CLOSE.
If the relay operates (the relay’s LED is on) the contacts between the Normally Closed and Common will OPEN (ex: RL4, 9&10)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
+24 Gnd Z-1 Z-2 Z-3 Timer Relay All Det Relay
Mute P/B
Gnd +12
Not
+10,0
DC or Relay Relay Relay 4 5
(Remote)
or DC
used
Low
-24 C NO C NO C NO NC C NO NC C NO
-12 Batt
Mute can be set for 10, 20,
30 or 60 minutes
The Timer Relay for lights and other devices
can be set for a quick 1.5 seconds, or for
5, 30 or 60 minutes.
If using Zoning (JP3 Pin is pulled off and 2 or 3
sensor/transmitters are used)
•
Zone 1 Chime = Ding Dong
•
Zone 2 Chime = Ding Ding Ding
•
Zone 3 Chime = Dong Ding Dong
9
DA-700 Control Panel Terminals