3.10 AC Wiring

 

The full AC pass-thru capacity of the MS-AE Series inverter/charger is 30 amps for both AC legs 

(AC HOT 1 and AC HOT 2). To obtain the full pass-thru capability of the inverter and protect the 

inverter’s pass-thru relay, use a maximum 30 amp double-pole breaker, which corresponds to a 

cable size of #8 AWG (THHN) in conduit. If you are using other wire sizes, please refer to your 

local electrical code for breaker requirements.

 

Pre-AC Wring Checklist

 

 

•  AC input to the inverter requires a maximum 30 amp circuit-breaker to each of the inverter’s 

AC Hot inputs. If the dual-pole AC input disconnect in the E-Panel is rated for 30 amps, it will 

meet this requirement.

 

•  AC Loads powered by the inverter will need to installed into an electrical sub-panel; or optional 

branch-rated breakers may be may be installed in the E-Panel and used to power these AC 

loads.

 

•  Always use properly rated circuit-breakers. If using an electrical sub-panel, circuit breakers 

can be moved from the main electrical panel to the sub-panel only if the breakers are also 

listed to be installed in the sub-panel.

 

•  AC wiring must be no less than 10 AWG (5.3 mm

2

) gauge copper wire and be approved for 

residential wiring per the NEC (THHN as an example).

 

Connecting the AC wires

 

Connecting E-Panel AC Input/Output Wires (refer to Figure 12 and 14 for the following steps):

 

1. Route two wires [AC hot 1 (black/L1) and AC hot 2 (red/L2)] from a double-pole circuit breaker 

in  the  main  panel  and connect  to  the  AC  HOT  IN  1  and  AC  HOT  IN  2  bus-bars  in  the  E-Panel 

respectively.

 

2. Route a wire from the neutral bus-bar in the main panel and connect to the NEUTRAL bus-bar 
in the E-Panel.

 

3. Route a wire from the ground bus-bar in the main panel and connect to the GROUND bus-bar 

in the E-panel.

 

4. Route wires from the AC HOT OUT 1 (black/L1), AC HOT  OUT 2 (red/Leg 2), NEUTRAL and 
GROUND bus-bars in the E-Panel and either connect to: A) the sub-panel, or B) to each individual 

circuit breaker if installed in the E-Panel.

 

Connecting to the Inverter AC terminals

 

Before connecting the wires to the inverter’s AC terminal block: 1. Ensure the wires are routed 

through the 3.5” grommet in the door; and 2. Establish the correct length of wire by opening and 

closing the door, then cut back the wires as required.

 

Info: 

Remove the AC access cover to expose the AC terminal block in the MS-AE Series

 

Inverter as described in owner’s manual.

 

For the following steps, refer to figure 4-5 to locate the #8 AWG wires in the E-Panel:

 

1. Connect the black wire labeled AC HOT OUT to the inverter’s AC HOT OUT 1 terminal.

 

2. Connect the red wire labeled AC HOT OUT to the inverter’s AC HOT OUT 2 terminal.

 

3. Connect the white wire from the NEUTRAL bus-bar in the E-Panel to either one of the inverter’s

 

AC NEUTRAL terminals.

 

4. Connect the black wire labeled AC HOT IN to the inverter’s AC HOT IN 1 terminal.

 

5. Connect the red wire labeled AC HOT IN to the inverter’s AC HOT IN 2 terminal.

 

Info: 

A ground wire from the E-Panel to the inverter AC ground terminal is not required, 

because the inverter is sufficiently grounded through the E-Panel to the permanent ground 

system. A ground wire may be connected from the GROUND bus-bar in the E-Panel to the 

inverter’s AC GROUND for additional redundancy.

 

Содержание MNE-240 Series

Страница 1: ...1 P a g e 1 0 0 2 9 1 R E V D MNE 240 E PANEL INSTRUCTIONS MNE 240 240 Volt Magnum PAE E Panel Owner s Manual...

Страница 2: ...parks in the vicinity of the batteries when using vented batteries Provide ventilation to clear the area of explosive gases Sealed AGM and Gel batteries do not under normal conditions create explosive...

Страница 3: ...couver Pour toute r paration ou service d entretien consulter un agent sp cialis Il y a peut tre plusieurs sources d alimentation dans cette system D brancher toutes les interrupteurs avant toute d en...

Страница 4: ...e AC and DC wiring bus bars and disconnects required to connect the Magnum MS PAE Series inverter charger system It also provides additional room to install additional equipment such as the MidNite Cl...

Страница 5: ...round Bus bar ME BMK Battery Monitor MS PAE Series Inverter Charger 500A 50mV Shunt Charge Controller DC Cover Positive and Negative Inverter Cables Inverter AC input Output Wires Door Grommet 3 5 Low...

Страница 6: ...our installation Info Installations should be performed by qualified personnel such as a licensed or certified electrician It is the installer s responsibility to determine which safety codes apply an...

Страница 7: ...7 P a g e 1 0 0 2 9 1 R E V D MNE 240 E PANEL INSTRUCTIONS Figure 2 MNE 240 Series E Panel System Wiring Diagram...

Страница 8: ...UIT KNOCKOUTS ARE MIRROR IMAGE OF BOTTOM KNOCKOUTS 4 67 12 90 22 37 0 75 17 00 4 17 INSIDE 1 13 3 4 CONDUIT INSIDE 1 38 1 CONDUIT 24 91 26 45 INSIDE 0 87 1 2 CONDUIT INSIDE 2 47 2 CONDUIT 25 55 0 87 1...

Страница 9: ...ons after an hour and also conduct a pull test You may be surprised that what you thought was a tight connection actually pulls out with little effort Copper is a relatively soft metal and will contin...

Страница 10: ...bustible fluid or components i e paper cloth plastic etc that may be ignited by heat sparks or flames they must be at a minimum distance of 2 feet away from the E Panel inverter his E Panel system wil...

Страница 11: ...ol P WR FA U LT C H G I N V SELE CT C H A R G ER Magnum Inverter Charger MidNite Solar Classic Controller MNE 240 Series E Panel I NV E RTER S HO RE AG S M E TE R S E T UP TEC H Bottom Mounting Bracke...

Страница 12: ...h E Panel Mounted Figure 8 Securing the Inverter to the E Panel Door As shown in figure 8 secure the inverter to the E Panel door using six 6 mm x 20 mm taptite thread forming pan head Phillips screws...

Страница 13: ...to the wiring terminals All wiring within the E Panel enclosure except low voltage control wiring shall be rated at least 250V or a combination of 250V e g 125V cable enclosed in 125V insulation heat...

Страница 14: ...tion DC CONNECTIONS DC CONNECTIONS E Panel with Left Hand Door E Panel with Right Hand Door Figure 12 E Panel Wiring Connections AC Wiring Connections The AC Bus Bars for neutral and hot connections h...

Страница 15: ...negative and positive terminals before turning ON the DC battery breaker or damage will occur The inverter s warranty doesn t cover repair to the inverter from this damage Caution The battery bank vol...

Страница 16: ...onnect to inverter DC Negative from shunt to inverter Wire Grommet snapped into door DC Ground from battery to E Panel from battery to disconnect Battery Temp Sensor from battery to inverter 12V 12V B...

Страница 17: ...1 and AC HOT IN 2 bus bars in the E Panel respectively 2 Route a wire from the neutral bus bar in the main panel and connect to the NEUTRAL bus bar in the E Panel 3 Route a wire from the ground bus ba...

Страница 18: ...F F Main Panel Utility Generator Input ON OFF AC Output Wiring AC Input Wiring 120 240VAC from Main Panel to AC HOT IN and NEUTRAL Bus bars AC Output Wiring a Wire to an electrical sub panel or b Use...

Страница 19: ...N O F F I N VERTER SHO R E A G S M E TE R SE TU P TE C H ME RC ME ARC Remote Control GROUND MS PAE Series Inverter Charger 3 5 Wire Grommet snapped into door AC Inverter wires pre wired in the E Pane...

Страница 20: ...heir connecting cables through the E Panel and pass through the small snap in grommet in the door to the RJ11 Ports on the inverter Automatic Generator Start Controller ME AGS for automatic generator...

Страница 21: ...tage should be 240 Vac 3 B Testing the E Panel AC Input Output Wiring 1 If the Inverter AC output voltages are correct tested above a turn the inverter OFF b slide the Inverter Bypass switch to the BY...

Страница 22: ...3 120VAC 3 120VAC 3 120VAC 3 240VAC 3 240VAC 3 E Panel with Left Hand Door E Panel with Right Hand Door B Testing the E Panel AC Input Output wiring Inverter is OFF Utility or Generator power to E Pan...

Страница 23: ...erter turned off the inverter the connected loads or any other installed equipment beyond the E Panel can be serviced Inverter Bypass Switch The Inverter Bypass Switch allows the incoming AC power uti...

Страница 24: ...the Bypass mode the power from the utility or generator routes through the Inverter Bypass Switch directly to the sub panel This mode allows the AC power to bypass the inverter and continue powering...

Страница 25: ...8223 360 403 7207 Purchasers must prepay all delivery costs or shipping charges to return any defective MidNite Solar product under this warranty policy Except for the warranty that the products are m...

Отзывы: