MNE-240 E-PANEL INSTRUCTIONS

 

 

 
 

 

3.7 Wiring the E-Panel and Inverter

 

Review the following information prior to wiring the E-Panel it is imperative that the following steps 

be taken to help reduce the risk of electric shock to you and damage to the E-Panel/inverter.

 

 

1.   Disconnect the main AC panel that will feed the E-Panel (if using utility power) by switching 

off the main circuit breaker. Lock out the AC breaker box to ensure no one will accidentally turn 

the power on during the installation process. If the AC panel does not have provision for locking 

the breaker box, place a sign on the box and tape the door closed to warn others from opening 

or turning on the AC panel.

 

 

2.   Place the main DC shutoff breaker (DC disconnect) in the OFF position.

 

 

3.   If additional breakers are installed, place them in the OFF position.

 

 

4.   Turn the inverter bypass switch to the “BYPASS” position (see the label on the bypass switch).

 

 

Pre-Wiring Requirements

 

•   All wiring and installations methods should conform to applicable electrical and building codes.

 

•  Always  check  for  existing  electrical,  plumbing  or  other  areas  of  potential  damage  prior  to 

making cuts in structural surfaces or walls.

 

•   Make sure all wires have a smooth bend radius and do not become kinked.

 

•   Both AC and DC overcurrent protection must be provided in this installation.

 

•  Use only copper wires with a minimum temperature rating of 75° C (176° F) to connect to the 

wiring terminals.

 

•   All wiring within the E-Panel enclosure, except low voltage control wiring, shall be rated at least

 

250V or a combination of 250V (e.g., 125V cable enclosed in 125V insulation/heat shrink).

 

•  All wiring to the battery terminals should be checked periodically (once a month) for proper 

tightness.

 

 

Install the Door Grommets

 

All wires that need to pass through the door of the E-Panel must 

be routed through the provided serrated snap-in grommets. These 

grommets help minimize wire insulation damage such as chafing, 

which  can  be  caused  by  constant  rubbing  when  opening  and 

closing  the  door.  A  3.5”  plastic  grommet  is  supplied  and  should 

be snapped into the larger hole in the door as shown in figure 11. 

The smaller 1” hole can be used for small signal wires (e.g. remote 

communications wire, battery temperature sensor cable, etc.), but 

no grommet is provided. It is important to route the wires so the 

door closes freely without undue force.

 

 

Grounding

 

 

 

 

Figure 11, Installing 3.5” 

Grommet in the Door

 

The E-Panel should be connected to a grounded, permanent wiring system.

 

 

DC Grounding - The negative battery conductor should be bonded to the grounding system at 

only one point in the system. The size for the conductor is usually determined by the size of the 

DC overcurrent protection (DC disconnect) per the NEC/CEC.

 

If the MNDC-GFP ground fault protector is installed, DO NOT connect battery negative to ground

 

- this connection is accomplished by the MNDC-GFP. Any additional DC grounding will make the

 

MNDC-GFP inoperative.

 

AC Grounding - The AC neutral and ground should only be bonded at the main service panel for 

the AC system.

 

Содержание MNE-240 Series

Страница 1: ...1 P a g e 1 0 0 2 9 1 R E V D MNE 240 E PANEL INSTRUCTIONS MNE 240 240 Volt Magnum PAE E Panel Owner s Manual...

Страница 2: ...parks in the vicinity of the batteries when using vented batteries Provide ventilation to clear the area of explosive gases Sealed AGM and Gel batteries do not under normal conditions create explosive...

Страница 3: ...couver Pour toute r paration ou service d entretien consulter un agent sp cialis Il y a peut tre plusieurs sources d alimentation dans cette system D brancher toutes les interrupteurs avant toute d en...

Страница 4: ...e AC and DC wiring bus bars and disconnects required to connect the Magnum MS PAE Series inverter charger system It also provides additional room to install additional equipment such as the MidNite Cl...

Страница 5: ...round Bus bar ME BMK Battery Monitor MS PAE Series Inverter Charger 500A 50mV Shunt Charge Controller DC Cover Positive and Negative Inverter Cables Inverter AC input Output Wires Door Grommet 3 5 Low...

Страница 6: ...our installation Info Installations should be performed by qualified personnel such as a licensed or certified electrician It is the installer s responsibility to determine which safety codes apply an...

Страница 7: ...7 P a g e 1 0 0 2 9 1 R E V D MNE 240 E PANEL INSTRUCTIONS Figure 2 MNE 240 Series E Panel System Wiring Diagram...

Страница 8: ...UIT KNOCKOUTS ARE MIRROR IMAGE OF BOTTOM KNOCKOUTS 4 67 12 90 22 37 0 75 17 00 4 17 INSIDE 1 13 3 4 CONDUIT INSIDE 1 38 1 CONDUIT 24 91 26 45 INSIDE 0 87 1 2 CONDUIT INSIDE 2 47 2 CONDUIT 25 55 0 87 1...

Страница 9: ...ons after an hour and also conduct a pull test You may be surprised that what you thought was a tight connection actually pulls out with little effort Copper is a relatively soft metal and will contin...

Страница 10: ...bustible fluid or components i e paper cloth plastic etc that may be ignited by heat sparks or flames they must be at a minimum distance of 2 feet away from the E Panel inverter his E Panel system wil...

Страница 11: ...ol P WR FA U LT C H G I N V SELE CT C H A R G ER Magnum Inverter Charger MidNite Solar Classic Controller MNE 240 Series E Panel I NV E RTER S HO RE AG S M E TE R S E T UP TEC H Bottom Mounting Bracke...

Страница 12: ...h E Panel Mounted Figure 8 Securing the Inverter to the E Panel Door As shown in figure 8 secure the inverter to the E Panel door using six 6 mm x 20 mm taptite thread forming pan head Phillips screws...

Страница 13: ...to the wiring terminals All wiring within the E Panel enclosure except low voltage control wiring shall be rated at least 250V or a combination of 250V e g 125V cable enclosed in 125V insulation heat...

Страница 14: ...tion DC CONNECTIONS DC CONNECTIONS E Panel with Left Hand Door E Panel with Right Hand Door Figure 12 E Panel Wiring Connections AC Wiring Connections The AC Bus Bars for neutral and hot connections h...

Страница 15: ...negative and positive terminals before turning ON the DC battery breaker or damage will occur The inverter s warranty doesn t cover repair to the inverter from this damage Caution The battery bank vol...

Страница 16: ...onnect to inverter DC Negative from shunt to inverter Wire Grommet snapped into door DC Ground from battery to E Panel from battery to disconnect Battery Temp Sensor from battery to inverter 12V 12V B...

Страница 17: ...1 and AC HOT IN 2 bus bars in the E Panel respectively 2 Route a wire from the neutral bus bar in the main panel and connect to the NEUTRAL bus bar in the E Panel 3 Route a wire from the ground bus ba...

Страница 18: ...F F Main Panel Utility Generator Input ON OFF AC Output Wiring AC Input Wiring 120 240VAC from Main Panel to AC HOT IN and NEUTRAL Bus bars AC Output Wiring a Wire to an electrical sub panel or b Use...

Страница 19: ...N O F F I N VERTER SHO R E A G S M E TE R SE TU P TE C H ME RC ME ARC Remote Control GROUND MS PAE Series Inverter Charger 3 5 Wire Grommet snapped into door AC Inverter wires pre wired in the E Pane...

Страница 20: ...heir connecting cables through the E Panel and pass through the small snap in grommet in the door to the RJ11 Ports on the inverter Automatic Generator Start Controller ME AGS for automatic generator...

Страница 21: ...tage should be 240 Vac 3 B Testing the E Panel AC Input Output Wiring 1 If the Inverter AC output voltages are correct tested above a turn the inverter OFF b slide the Inverter Bypass switch to the BY...

Страница 22: ...3 120VAC 3 120VAC 3 120VAC 3 240VAC 3 240VAC 3 E Panel with Left Hand Door E Panel with Right Hand Door B Testing the E Panel AC Input Output wiring Inverter is OFF Utility or Generator power to E Pan...

Страница 23: ...erter turned off the inverter the connected loads or any other installed equipment beyond the E Panel can be serviced Inverter Bypass Switch The Inverter Bypass Switch allows the incoming AC power uti...

Страница 24: ...the Bypass mode the power from the utility or generator routes through the Inverter Bypass Switch directly to the sub panel This mode allows the AC power to bypass the inverter and continue powering...

Страница 25: ...8223 360 403 7207 Purchasers must prepay all delivery costs or shipping charges to return any defective MidNite Solar product under this warranty policy Except for the warranty that the products are m...

Отзывы: