Refrigerant pipe installation
96
Installation
Pipe diameter
Flare dimension A (mm)
Flare shape
Min
Max
1/4" (6.35)
8.3
8.7
R0.4~0.8
A
45°
90
°
4
-+
3/8" (9.52)
12.0
12.4
1/2" (12.7)
15.4
15.8
5/8" (15.9)
18.6
19.1
3/4" (19)
22.9
23.3
After flared the pipe, the opening part must be seal by end cover or adhesive tape to avoid duct or
exogenous impurity come into the pipe.
5.2.7 Drill holes if the pipes need to pass the wall.
5.2.8 According to the field condition to bend the pipes so that it can pass the wall smoothly.
5.2.9 Bind and wrap the wire together with the insulated pipe if necessary.
5.2.10 Set the wall conduit
5.2.11 Set the supporter for the pipe.
5.2.12 Locate the pipe and fix it by supporter
For horizontal refrigerant pipe, the distance between supporters should not be exceed 1m.
For vertical refrigerant pipe, the distance between supporters should not be exceed 1.5m.
5.2.13 Connect the pipe to indoor unit and outdoor unit by using two spanners.
Be sure to use two spanners and proper torque to fasten the nut, too large torque will damage the
bellmouthing, and too small torque may cause leakage. Refer the following table for different pipe
connection.
Pipe Diameter
Torque
Sketch map
(kgf.cm)
(N.cm)
1/4" (6.35)
144~176
1420~1720
3/8" (9.52)
333~407
3270~3990
1/2" (12.7)
504~616
4950~6030
5/8" (15.9)
630~770
6180~7540
3/4" (19)
990~1210
9270~11860
5.3 For Units with Twins Function
5.3.1 Length and drop height permitted of the refrigerant piping
Note: Reduced length of the branching tube is the 0.5m of the equivalent length of the pipe.
Содержание U2MRS-12
Страница 6: ...Dimensions 12 Indoor Units 2 Dimensions Model A H 18 K 205 235 24 K 30 K 245 275 36 K 245 275 205 235...
Страница 7: ...Service Space Indoor Units 13 3 Service Space 1000mm 1000mm 1000mm 1000m m...
Страница 13: ...Field Wiring Indoor Units 19 9 Field Wiring...
Страница 20: ...Wiring Diagrams 26 Indoor Units 4 Wiring Diagrams 12K 12K 24K 30K 36K...
Страница 21: ...Wiring Diagrams Indoor Units 27 MTB 24HWDN1 QRC4...
Страница 28: ...Field Wiring 34 Indoor Units 10 Field Wiring 12K 18K 24K 30K 36K...
Страница 32: ...Service Space 38 Indoor Units 3 Service Space...
Страница 34: ...Wiring Diagrams 40 Indoor Units 36K...
Страница 37: ...Indoor Units 43 9 Field Wiring...
Страница 40: ...Dimensions 46 Indoor Units 2 Dimensions...
Страница 41: ...Service Space Indoor Units 47 3 Service Space...
Страница 42: ...Wiring Diagrams 48 Indoor Units 4 Wiring Diagrams 12K 18K...
Страница 46: ...52 Indoor Units 10 Field Wiring 12K 18K...
Страница 48: ......
Страница 51: ...Dimensions Console Type 57 2 Dimensions MFAU 12HRFN1 QRC8 MFA 16HRFN1 QRC8...
Страница 52: ...Service Space 58 Console Type 3 Service Space...
Страница 53: ...Wiring Diagrams Console Type 59 4 Wiring Diagrams MFAU 12HRFN1 QRC8 MFA 16HRFN1 QRC8...
Страница 58: ...Field Wiring 64 Console Type 10 Field Wiring MFAU 12HRFN1 QRC8 MFA 16HRFN1 QRC8...
Страница 64: ...Wiring Diagrams 70 Outdoor Units 4 Wiring Diagrams U2MRS 12...
Страница 65: ...Wiring Diagrams Outdoor Units 71 18K 24K 30K 36K...
Страница 66: ...Wiring Diagrams 72 Outdoor Units...
Страница 67: ...Wiring Diagrams Outdoor Units 73...
Страница 92: ...Refrigerant pipe installation 98 Installation...
Страница 123: ...Troubleshooting Electrical Control System 129 2 4 1 2 Outdoor unit malfunction...
Страница 130: ...Troubleshooting 136 Electrical Control System 2 4 2 3 Up down panel is not closed...
Страница 132: ...Troubleshooting 138 Electrical Control System 2 4 4 For the outdoor unit 2 4 4 1 E0 malfunction...
Страница 134: ...Troubleshooting 140 Electrical Control System 2 4 4 3 E3 malfunction...
Страница 135: ...Troubleshooting Electrical Control System 141 2 4 4 4 E4 malfunction...
Страница 138: ...Troubleshooting 144 Electrical Control System 2 4 4 7 E6 malfunction Only for MOU 36HFN1 QRC4 MOU 36HFN1 QRC8...
Страница 141: ...Troubleshooting Electrical Control System 147 2 4 4 9 P1 malfunction For 36k models...
Страница 142: ...Troubleshooting 148 Electrical Control System 2 4 4 10 P2 malfunction For 36k models...
Страница 143: ...Troubleshooting Electrical Control System 149 2 4 4 11 P3 malfunction...