Electrical Control Function
Electrical Control System
119
1.3.5 Drying mode
For 12K units:
Indoor fan speed is fixed at breeze and can’t be changed. The louver angle is the same as in cooling mode.
Low indoor room temperature protection
In drying mode, if room temperature is lower than 10
℃
, the compressor will stop and not resume until room
temperature exceeds 12
℃
.
All protections are active and the same as that in cooling mode.
For other units: Drying mode works the same as cooling mode in low speed.
All protections are active and the same as that in cooling mode.
1.3.6 Timer function
1.3.6.1 Timing range is 24 hours.
1.3.6.2 Timer on. The machine will turn on automatically when reaching the setting time.
1.3.6.3 Timer off. The machine will turn off automatically when reaching the setting time.
1.3.6.4 Timer on/off. The machine will turn on automatically when reaching the setting “on” time, and then
turn off automatically when reaching the setting “off” time.
1.3.6.5 Timer off/on. The machine will turn off automatically when reaching the setting “off” time, and then
turn on automatically when reaching the setting “on” time.
1.3.6.6 The timer function will not change the AC current operation mode. Suppose AC is off now, it will not
start up firstly after setting the “timer off” function. And when reaching the setting time, the timer LED will be
off and the AC running mode has not been changed.
1.3.6.7 The setting time is relative time.
1.3.7 Economy function
1.3.7.1 The sleep function is available in cooling, heating or auto mode.
1.3.7.2. Operation process in sleep mode is as follow:
When cooling, the setting temperature rises 1
℃
(be lower than 30
℃
) every one hour, 2 hours later the
setting temperature stops rising and the indoor fan is fixed at low speed.
When heating, the setting temperature decreases 1
℃
(be higher than 17
℃
) every one hour, 2 hours later
the setting temperature stops rising and indoor fan is fixed at low speed. (Anti-cold wind function has the
priority).
1.3.7.3 Operation time in sleep mode is 7 hours. After 7 hours the AC quits this mode but doesn’t turns off,
but for console, the unit will turn off.
1.3.7.4 Timer setting is available
1.3.8 Auto-Restart function
The indoor unit is equipped with auto-restart function, which is carried out through an auto-restart module. In
case of a sudden power failure, the module memorizes the setting conditions before the power failure. The
unit will resume the previous operation setting (not including Swing function) automatically after 3 minutes
when power returns.
Содержание U2MRS-12
Страница 6: ...Dimensions 12 Indoor Units 2 Dimensions Model A H 18 K 205 235 24 K 30 K 245 275 36 K 245 275 205 235...
Страница 7: ...Service Space Indoor Units 13 3 Service Space 1000mm 1000mm 1000mm 1000m m...
Страница 13: ...Field Wiring Indoor Units 19 9 Field Wiring...
Страница 20: ...Wiring Diagrams 26 Indoor Units 4 Wiring Diagrams 12K 12K 24K 30K 36K...
Страница 21: ...Wiring Diagrams Indoor Units 27 MTB 24HWDN1 QRC4...
Страница 28: ...Field Wiring 34 Indoor Units 10 Field Wiring 12K 18K 24K 30K 36K...
Страница 32: ...Service Space 38 Indoor Units 3 Service Space...
Страница 34: ...Wiring Diagrams 40 Indoor Units 36K...
Страница 37: ...Indoor Units 43 9 Field Wiring...
Страница 40: ...Dimensions 46 Indoor Units 2 Dimensions...
Страница 41: ...Service Space Indoor Units 47 3 Service Space...
Страница 42: ...Wiring Diagrams 48 Indoor Units 4 Wiring Diagrams 12K 18K...
Страница 46: ...52 Indoor Units 10 Field Wiring 12K 18K...
Страница 48: ......
Страница 51: ...Dimensions Console Type 57 2 Dimensions MFAU 12HRFN1 QRC8 MFA 16HRFN1 QRC8...
Страница 52: ...Service Space 58 Console Type 3 Service Space...
Страница 53: ...Wiring Diagrams Console Type 59 4 Wiring Diagrams MFAU 12HRFN1 QRC8 MFA 16HRFN1 QRC8...
Страница 58: ...Field Wiring 64 Console Type 10 Field Wiring MFAU 12HRFN1 QRC8 MFA 16HRFN1 QRC8...
Страница 64: ...Wiring Diagrams 70 Outdoor Units 4 Wiring Diagrams U2MRS 12...
Страница 65: ...Wiring Diagrams Outdoor Units 71 18K 24K 30K 36K...
Страница 66: ...Wiring Diagrams 72 Outdoor Units...
Страница 67: ...Wiring Diagrams Outdoor Units 73...
Страница 92: ...Refrigerant pipe installation 98 Installation...
Страница 123: ...Troubleshooting Electrical Control System 129 2 4 1 2 Outdoor unit malfunction...
Страница 130: ...Troubleshooting 136 Electrical Control System 2 4 2 3 Up down panel is not closed...
Страница 132: ...Troubleshooting 138 Electrical Control System 2 4 4 For the outdoor unit 2 4 4 1 E0 malfunction...
Страница 134: ...Troubleshooting 140 Electrical Control System 2 4 4 3 E3 malfunction...
Страница 135: ...Troubleshooting Electrical Control System 141 2 4 4 4 E4 malfunction...
Страница 138: ...Troubleshooting 144 Electrical Control System 2 4 4 7 E6 malfunction Only for MOU 36HFN1 QRC4 MOU 36HFN1 QRC8...
Страница 141: ...Troubleshooting Electrical Control System 147 2 4 4 9 P1 malfunction For 36k models...
Страница 142: ...Troubleshooting 148 Electrical Control System 2 4 4 10 P2 malfunction For 36k models...
Страница 143: ...Troubleshooting Electrical Control System 149 2 4 4 11 P3 malfunction...