Troubleshooting
Electrical Control System
133
the value is not 5V, change the PCB. Otherwise, go to step 3.
3) Rotate the fan by hand, measure the voltage of pin1-5, pin 2-5 and pin 3-5 in feedback signal connector.
If any voltage is not positive voltage fluctuation, the fan motor must has problems and need to be
replaced.
Index2:
1. Indoor DC fan motor(control chip is inside fan motor)
Power on and when the unit is in standby, measure the voltage of pin1-pin3, pin4-pin3 in fan motor
connector. If the value of the voltage is not in the range showing in below table, the PCB must have
problems and need to be replaced.
For other models:
DC motor voltage input and output
NO. Color Signal Voltage
1 Red Vs/Vm
192V~380V
2 ---
---
---
3 Black GND
0V
4 White Vcc 13.5-16.5V
5 Yellow Vsp 0~6.5V
6 Blue FG
15V
For console:
5
4
6
3
2
1
DC motor voltage input and output
NO. Color
Signal
Voltage
1 Red
V
DC
310V
2
---
---
---
3
White
Vcc
15V
4 Blue
FG
15V
5 Yellow
Vsp
0-7.5V
6
Black
GND
0V
Содержание U2MRS-12
Страница 6: ...Dimensions 12 Indoor Units 2 Dimensions Model A H 18 K 205 235 24 K 30 K 245 275 36 K 245 275 205 235...
Страница 7: ...Service Space Indoor Units 13 3 Service Space 1000mm 1000mm 1000mm 1000m m...
Страница 13: ...Field Wiring Indoor Units 19 9 Field Wiring...
Страница 20: ...Wiring Diagrams 26 Indoor Units 4 Wiring Diagrams 12K 12K 24K 30K 36K...
Страница 21: ...Wiring Diagrams Indoor Units 27 MTB 24HWDN1 QRC4...
Страница 28: ...Field Wiring 34 Indoor Units 10 Field Wiring 12K 18K 24K 30K 36K...
Страница 32: ...Service Space 38 Indoor Units 3 Service Space...
Страница 34: ...Wiring Diagrams 40 Indoor Units 36K...
Страница 37: ...Indoor Units 43 9 Field Wiring...
Страница 40: ...Dimensions 46 Indoor Units 2 Dimensions...
Страница 41: ...Service Space Indoor Units 47 3 Service Space...
Страница 42: ...Wiring Diagrams 48 Indoor Units 4 Wiring Diagrams 12K 18K...
Страница 46: ...52 Indoor Units 10 Field Wiring 12K 18K...
Страница 48: ......
Страница 51: ...Dimensions Console Type 57 2 Dimensions MFAU 12HRFN1 QRC8 MFA 16HRFN1 QRC8...
Страница 52: ...Service Space 58 Console Type 3 Service Space...
Страница 53: ...Wiring Diagrams Console Type 59 4 Wiring Diagrams MFAU 12HRFN1 QRC8 MFA 16HRFN1 QRC8...
Страница 58: ...Field Wiring 64 Console Type 10 Field Wiring MFAU 12HRFN1 QRC8 MFA 16HRFN1 QRC8...
Страница 64: ...Wiring Diagrams 70 Outdoor Units 4 Wiring Diagrams U2MRS 12...
Страница 65: ...Wiring Diagrams Outdoor Units 71 18K 24K 30K 36K...
Страница 66: ...Wiring Diagrams 72 Outdoor Units...
Страница 67: ...Wiring Diagrams Outdoor Units 73...
Страница 92: ...Refrigerant pipe installation 98 Installation...
Страница 123: ...Troubleshooting Electrical Control System 129 2 4 1 2 Outdoor unit malfunction...
Страница 130: ...Troubleshooting 136 Electrical Control System 2 4 2 3 Up down panel is not closed...
Страница 132: ...Troubleshooting 138 Electrical Control System 2 4 4 For the outdoor unit 2 4 4 1 E0 malfunction...
Страница 134: ...Troubleshooting 140 Electrical Control System 2 4 4 3 E3 malfunction...
Страница 135: ...Troubleshooting Electrical Control System 141 2 4 4 4 E4 malfunction...
Страница 138: ...Troubleshooting 144 Electrical Control System 2 4 4 7 E6 malfunction Only for MOU 36HFN1 QRC4 MOU 36HFN1 QRC8...
Страница 141: ...Troubleshooting Electrical Control System 147 2 4 4 9 P1 malfunction For 36k models...
Страница 142: ...Troubleshooting 148 Electrical Control System 2 4 4 10 P2 malfunction For 36k models...
Страница 143: ...Troubleshooting Electrical Control System 149 2 4 4 11 P3 malfunction...