86
Enquiry
information
Display value
Meaning
Remark
T1,T2,T3,T4,
T2B,TP,TH,
Targeted
Frequency,
Actual
Frequency
-1F,-1E,-1d,-1c,-
1b,-1A
-25,-24,-23,-22,-21,-2
0
1. All the displaying temperature is actual
value.
2. All the temperature is °C no matter what
kind of remote controller is used.
3. T1,T2,T3,T4,T2B display range:-25~70,
TP display range:-20~130.
4. Frequency display range: 0~159HZ.
5. If the actual value exceeds the range, it
will display the maximum value or minimum
value.
-19
—
99
-19
—
99
A0,A1,…A9
100,101,…109
b0,b1,…b9
110,111,…119
c0,c1,…c9
120,121,…129
d0,d1,…d9
130,131,…139
E0,E1,…E9
140,141,…149
F0,F1,…F9
150,151,…159
Indoor fan
speed
/Outdoor fan
speed
0
OFF
1,2,3,4
Low speed, Medium
speed, High speed,
Turbo
For some big capacity motors.
14-FF
Actual fan
speed=Display value
turns to decimal
value and then
multiply 10. The unit
is RPM.
For some small capacity motors,
display value is from 14-FF(hexadecimal),
the corresponding fan speed range is from
200-2550RPM.
EXV opening
angle
0-FF
Actual EXV opening
value=Display value
turns to decimal
value and then
multiply 2.
Compressor
continuous
running time
0-FF
0-255 minutes
If the actual value exceeds the
range, it will display the maximum
value or minimum value.
Causes of
compressor
stop.
0-99
For the detailed
meaning, please
consult with engineer
Decimal display
Reserve
0-FF
Содержание MUE-48HRFN1-M
Страница 8: ...5 2 2 Part names of Indoor Outdoor units Cassette Unit...
Страница 9: ...6 Duct Units...
Страница 10: ...7 Console...
Страница 11: ...8 Ceiling floor Units...
Страница 28: ...25 Model W D H W1 A B MOE30U 48HFN1 M mm 952 415 1333 1045 634 404 inch 37 5 16 3 52 5 41 1 25 0 15 9...
Страница 30: ...27 Console Unit Ceiling floor Units...
Страница 34: ...31 CFAU 09HRFN1 M C CFAU 12HRFN1 M C MCD 36HRFN1 M C MCD 48HRFN1 M D...
Страница 35: ...32 CTBU 36HWFN1 M C CTBU 48HWFN1 M C...
Страница 36: ...33 MUEU 18HRFN1 M C MUEU 24HRFN1 M C MUE 36HRFN1 M C...
Страница 37: ...34 MUE 48HRFN1 M C MUE 36HRFN1 M C MUE 48HRFN1 M C...
Страница 39: ...36 MOBA30 09HFN1 MT0W MOB30 12HFN1 MT0W...
Страница 40: ...37 MOD30 24HFN1 MT0W MOD01 23HFN1 MT0W...
Страница 41: ...38 MOD30U 36HFN1 M...
Страница 47: ...44 CTBU 09HWFN1 M C Code 0 Code 1 Code 2 Code 3 Code 4...
Страница 48: ...45 CTBU 12HWFN1 M C Code 0 Code 1 Code 2 Code 3 Code 4...
Страница 49: ...46 CTBU 18HWFN1 M C Code 0 Code 1 Code 2 Code 3 Code 4...
Страница 50: ...47 CTBU 24HWFN1 M C Code 0 Code 1 Code 2 Code 3 Code 4...
Страница 51: ...48 CTB 36HWFN1 M C Code 0 Code 1 Code 2 Code 3 Code 4...
Страница 52: ...49 CTB 48HWFN1 M C Code 0 Code 1 Code 2 Code 3 Code 4...
Страница 61: ...58 12 Field Wiring 36K 48K...
Страница 106: ...103 P U P V...
Страница 107: ...104 P W P N...
Страница 123: ...120 4 Remove the evaporator support board 5 Screw off the fixing screws to remove the evaporator 4 screws 1 screw...
Страница 155: ...152 5 Remove the four fixing screws of the fan motor then remove the motor 5...
Страница 168: ...165 6 Remove the grounding screw 7 Remove the Wires 1 2 3 or L1 L2 S Then remove the electronic control box 5 7...