68
Pipe
diameter
Flare
dimension A
(mm)
Flare shape
Min
Max
1/4"
(6.35)
8.3
8.7
R0.4~0.8
A
45°
90
°
4
-+
3/8"
(9.52)
12.0
12.4
1/2"
(12.7)
15.4
15.8
5/8"
(15.9)
18.6
19.1
3/4" (19)
22.9
23.3
After flared the pipe, the opening part must
be seal by end cover or adhesive tape to
avoid duct or exogenous impurity come into
the pipe.
7. Drill holes if the pipes need to pass the
wall.
8. According to the field condition to bend the
pipes so that it can pass the wall smoothly.
9. Bind and wrap the wire together with the
insulated pipe if necessary.
10. Set the wall conduit
11. Set the supporter for the pipe.
12. Locate the pipe and fix it by supporter
For horizontal refrigerant pipe, the distance
between supporters should not be exceed
1m.
For vertical refrigerant pipe, the distance
between supporters should not be exceed
1.5m.
13. Connect the pipe to indoor unit and outdoor
unit by using two spanners.
Be sure to use two spanners and proper
torque to fasten the nut, too large torque
will damage the flare, and too small torque
may cause leakage. Refer the following
table for different pipe connection.
Pipe
Diameter
Torque
Sketch map
(kgf.cm)
(N.cm)
1/4" (6.35)
144~176
1420~1720
3/8" (9.52)
333~407
3270~3990
1/2" (12.7)
504~616
4950~6030
5/8" (15.9)
630~770
6180~7540
3/4" (19)
990~1210 9270~11860
12.4.3 First-Time Installation
Air and moisture in the refrigerant system
cause the following problems:
●
Increases in system pressure
●
Increases in operating current
●
Decreases in cooling and heating efficiency
●
Blocks in capillary tubing caused by
moisture in the refrigerant circuit freezing
●
Corrosion of parts in the refrigerant system
caused by water
The indoor units and the pipes between
indoor and outdoor units must be tested for
leakages and evacuated to remove gas and
moisture from the system.
Gas leak check with soap water:
Apply soap water or a liquid neutral
detergent on the connections with a soft brush
to check for leakage in the pipe connecting
points. If bubbles emerge, the pipes are
leaking.
1. Air Purging Using the Vacuum Pump
1) Completely tighten the flare nuts on the
indoor and outdoor units. Confirm that both
the2-way and 3-way valves are set to the
closed position.
2) Connect the charge hose with the push pin
of the Handle Lo to the 3-way valve gas
service port.
3) Connect the charge hose of the Handle Hi
to the vacuum pump.
4) Fully open the Handle Lo of the manifold
valve.
Содержание MUE-48HRFN1-M
Страница 8: ...5 2 2 Part names of Indoor Outdoor units Cassette Unit...
Страница 9: ...6 Duct Units...
Страница 10: ...7 Console...
Страница 11: ...8 Ceiling floor Units...
Страница 28: ...25 Model W D H W1 A B MOE30U 48HFN1 M mm 952 415 1333 1045 634 404 inch 37 5 16 3 52 5 41 1 25 0 15 9...
Страница 30: ...27 Console Unit Ceiling floor Units...
Страница 34: ...31 CFAU 09HRFN1 M C CFAU 12HRFN1 M C MCD 36HRFN1 M C MCD 48HRFN1 M D...
Страница 35: ...32 CTBU 36HWFN1 M C CTBU 48HWFN1 M C...
Страница 36: ...33 MUEU 18HRFN1 M C MUEU 24HRFN1 M C MUE 36HRFN1 M C...
Страница 37: ...34 MUE 48HRFN1 M C MUE 36HRFN1 M C MUE 48HRFN1 M C...
Страница 39: ...36 MOBA30 09HFN1 MT0W MOB30 12HFN1 MT0W...
Страница 40: ...37 MOD30 24HFN1 MT0W MOD01 23HFN1 MT0W...
Страница 41: ...38 MOD30U 36HFN1 M...
Страница 47: ...44 CTBU 09HWFN1 M C Code 0 Code 1 Code 2 Code 3 Code 4...
Страница 48: ...45 CTBU 12HWFN1 M C Code 0 Code 1 Code 2 Code 3 Code 4...
Страница 49: ...46 CTBU 18HWFN1 M C Code 0 Code 1 Code 2 Code 3 Code 4...
Страница 50: ...47 CTBU 24HWFN1 M C Code 0 Code 1 Code 2 Code 3 Code 4...
Страница 51: ...48 CTB 36HWFN1 M C Code 0 Code 1 Code 2 Code 3 Code 4...
Страница 52: ...49 CTB 48HWFN1 M C Code 0 Code 1 Code 2 Code 3 Code 4...
Страница 61: ...58 12 Field Wiring 36K 48K...
Страница 106: ...103 P U P V...
Страница 107: ...104 P W P N...
Страница 123: ...120 4 Remove the evaporator support board 5 Screw off the fixing screws to remove the evaporator 4 screws 1 screw...
Страница 155: ...152 5 Remove the four fixing screws of the fan motor then remove the motor 5...
Страница 168: ...165 6 Remove the grounding screw 7 Remove the Wires 1 2 3 or L1 L2 S Then remove the electronic control box 5 7...