81
3 times when fan motor restarts continuously,
the unit will stop and the LED will display the
failure.
When outdoor fan speed keeps too low (lower
than 100RPM) or too high (higher than
1500RPM) for 60s, the unit will stop and the
LED will display the failure. Malfunction is
cleared 30s later.
14.3.5 Inverter module protection
The Inverter module has a protection function
about current, voltage and temperature. If these
protections happen, the corresponding code
will display on indoor unit and the unit will stop
working.
14.3.6 Indoor fan delayed open function
When the unit starts up, the louver will be active
immediately and the indoor fan will open 10s
later.
If the unit runs in heating mode, the indoor fan
will be also controlled by anti-cold wind
function.
14.3.7 Compressor preheating functions
Preheating permitting condition:
If T4
<
3
℃
(37.4°F) and the machine connects
to power supply newly within 5 seconds or if T4
<
3
℃
(37.4°F) and compressor has stopped for
over 3 hours, the compressor heating cable will
work.
Preheating mode:
A weak current flow through the coil of
compressor from the wiring terminal of the
compressor, then the compressor is heated
without operation.
Preheating release condition:
If T4
≥
5
℃
(41°F) or the compressor starts
running, the preheating function will stop.
14.3.9 Condenser high temperature T3
protection
---55°C(131°F)<T3< 60°C(140°F),
the
compressor frequency will decrease to the
lower level until to F1 and then runs at F1.If
T3<54°C(129.2°F), the compressor will keep
running at the current frequency.
---T3<52°C(125.6°F), the compressor will not
limit the frequency and resume to the former
frequency.
---T3>60°C(140°F)
for
5
seconds,
the
compressor will stop until T3<52°C(125.6°F).
14.3.10 Evaporator low temperature T2
protection
---T2<0°C(32°F), the compressor will stop and
restart when T2
≧
5°C(41°F).
---0°C(32°F)
≦
T2<4°C(39.2 °F), the compressor
frequency will be limited and decreased to the
lower level
---
4°C(39.2°F)≤T2≤7°C(44.6°F),
the
compressor will keep the current frequency.
---T2>7°C(44.6°F), the compressor frequency
will not be limited.
14.4 Operation Modes and Functions
14.4.1 Fan mode
(1) Outdoor fan and compressor stop.
(2) Temperature setting function is disabled,
and no setting temperature is displayed.
(3) Indoor fan can be set to high/med/low/auto.
(4) The louver operates same as in cooling
mode.
(5) Auto fan:
a
b
c
d
6.0°C(42.8°F)
T1-24°C(75.2°F)
e
H
(H-L)*0.75+L
(H-L)*0.5+L
(H-L)*0.25+L
L
5.0°C(41.0°F)
4.0°C(39.2°F)
2.5°C(36.5°F)
1.0°C(33.8°F)
14.4.2 Cooling Mode
14.4.2.1 Outdoor fan running rules
T4
A
DC_FAN_HI_SPD_ADD
B
DC_FAN_MID_SPD_ADD
C
DC_FAN_MIN_SPD_ADD
D
DC_FAN_SLOW_SPD_ADD
E
DC_FAN_SSLOW_SPD_ADD
28
℃
(82.4°F)
19
℃
(66.2°F)
17
℃
(62.6°F)
26
℃
(78.8°F)
25
℃
(77°F)
23
℃
(73.4°F)
22
℃
(71.6°F)
20
℃
(69°F)
14.4.2.2 Indoor fan running rules
Содержание MUE-48HRFN1-M
Страница 8: ...5 2 2 Part names of Indoor Outdoor units Cassette Unit...
Страница 9: ...6 Duct Units...
Страница 10: ...7 Console...
Страница 11: ...8 Ceiling floor Units...
Страница 28: ...25 Model W D H W1 A B MOE30U 48HFN1 M mm 952 415 1333 1045 634 404 inch 37 5 16 3 52 5 41 1 25 0 15 9...
Страница 30: ...27 Console Unit Ceiling floor Units...
Страница 34: ...31 CFAU 09HRFN1 M C CFAU 12HRFN1 M C MCD 36HRFN1 M C MCD 48HRFN1 M D...
Страница 35: ...32 CTBU 36HWFN1 M C CTBU 48HWFN1 M C...
Страница 36: ...33 MUEU 18HRFN1 M C MUEU 24HRFN1 M C MUE 36HRFN1 M C...
Страница 37: ...34 MUE 48HRFN1 M C MUE 36HRFN1 M C MUE 48HRFN1 M C...
Страница 39: ...36 MOBA30 09HFN1 MT0W MOB30 12HFN1 MT0W...
Страница 40: ...37 MOD30 24HFN1 MT0W MOD01 23HFN1 MT0W...
Страница 41: ...38 MOD30U 36HFN1 M...
Страница 47: ...44 CTBU 09HWFN1 M C Code 0 Code 1 Code 2 Code 3 Code 4...
Страница 48: ...45 CTBU 12HWFN1 M C Code 0 Code 1 Code 2 Code 3 Code 4...
Страница 49: ...46 CTBU 18HWFN1 M C Code 0 Code 1 Code 2 Code 3 Code 4...
Страница 50: ...47 CTBU 24HWFN1 M C Code 0 Code 1 Code 2 Code 3 Code 4...
Страница 51: ...48 CTB 36HWFN1 M C Code 0 Code 1 Code 2 Code 3 Code 4...
Страница 52: ...49 CTB 48HWFN1 M C Code 0 Code 1 Code 2 Code 3 Code 4...
Страница 61: ...58 12 Field Wiring 36K 48K...
Страница 106: ...103 P U P V...
Страница 107: ...104 P W P N...
Страница 123: ...120 4 Remove the evaporator support board 5 Screw off the fixing screws to remove the evaporator 4 screws 1 screw...
Страница 155: ...152 5 Remove the four fixing screws of the fan motor then remove the motor 5...
Страница 168: ...165 6 Remove the grounding screw 7 Remove the Wires 1 2 3 or L1 L2 S Then remove the electronic control box 5 7...