90
For 36K-48K Outdoor Unit
No
Problems
Error Code
1
Communication malfunction between indoor and outdoor units
E1
2
Current overload protection
F0
3
Outdoor ambient temperature sensor (T4 ) malfunction
F1
4
Condenser coil temperature sensor (T3) malfunction
F2
5
Compressor discharge temperature sensor (T5) malfunction
F3
6
Outdoor unit EEPROM parameter error
F4
7
Outdoor fan speed malfunction
F5
8
Inverter module (IPM) malfunction
P0
9
Over-voltage or under-voltage protection
P1
10
Compressor top high temperature protection (OLP)
P2
11
Low ambient temperature cut off in heating
P3
12
Compressor drive malfunction
P4
13
High temperature protection of indoor coil in heating
J0
14
Outdoor temperature protection of outdoor coil in cooling
J1
15
Temperature protection of compressor discharge
J2
16
PFC module protection
J3
17
Communication malfunction between control board and IPM board
J4
18
High pressure protection
J5
19
Low pressure protection
J6
20
Outdoor IPM module temperature sensor malfunction
P7
21
AC voltage protection
J8
Outdoor check function
N
Display
Remark
00
Normal display
Display running frequency, running state or malfunction
code
01
Indoor unit capacity demand code
Actual data*HP*10
If capacity demand code is higher than 99, the digital display
tube will show single digit and tens digit. (For example, the
digital display tube show “5.0”,it means the capacity demand
is 15. the digital display tube show “60”,it means the
capacity demand is 6.0)
02
Amendatory capacity demand code
03
The frequency after the capacity requirement
transfer
04
The frequency after the frequency limit
05
The frequency of sending to 341 chip
06
Indoor unit evaporator outlet temp.(heating T2
,
cooling T2B)
If the temp. is lower than 0 degree, the digital display tube
will show “0”.If the
temp. is higher than 70 degree, the digital
display tube will show “70”.
07
Condenser pipe temp.(T3)
If the temp. is lower than -9 degree, the digital display tube
Содержание MUE-48HRFN1-M
Страница 8: ...5 2 2 Part names of Indoor Outdoor units Cassette Unit...
Страница 9: ...6 Duct Units...
Страница 10: ...7 Console...
Страница 11: ...8 Ceiling floor Units...
Страница 28: ...25 Model W D H W1 A B MOE30U 48HFN1 M mm 952 415 1333 1045 634 404 inch 37 5 16 3 52 5 41 1 25 0 15 9...
Страница 30: ...27 Console Unit Ceiling floor Units...
Страница 34: ...31 CFAU 09HRFN1 M C CFAU 12HRFN1 M C MCD 36HRFN1 M C MCD 48HRFN1 M D...
Страница 35: ...32 CTBU 36HWFN1 M C CTBU 48HWFN1 M C...
Страница 36: ...33 MUEU 18HRFN1 M C MUEU 24HRFN1 M C MUE 36HRFN1 M C...
Страница 37: ...34 MUE 48HRFN1 M C MUE 36HRFN1 M C MUE 48HRFN1 M C...
Страница 39: ...36 MOBA30 09HFN1 MT0W MOB30 12HFN1 MT0W...
Страница 40: ...37 MOD30 24HFN1 MT0W MOD01 23HFN1 MT0W...
Страница 41: ...38 MOD30U 36HFN1 M...
Страница 47: ...44 CTBU 09HWFN1 M C Code 0 Code 1 Code 2 Code 3 Code 4...
Страница 48: ...45 CTBU 12HWFN1 M C Code 0 Code 1 Code 2 Code 3 Code 4...
Страница 49: ...46 CTBU 18HWFN1 M C Code 0 Code 1 Code 2 Code 3 Code 4...
Страница 50: ...47 CTBU 24HWFN1 M C Code 0 Code 1 Code 2 Code 3 Code 4...
Страница 51: ...48 CTB 36HWFN1 M C Code 0 Code 1 Code 2 Code 3 Code 4...
Страница 52: ...49 CTB 48HWFN1 M C Code 0 Code 1 Code 2 Code 3 Code 4...
Страница 61: ...58 12 Field Wiring 36K 48K...
Страница 106: ...103 P U P V...
Страница 107: ...104 P W P N...
Страница 123: ...120 4 Remove the evaporator support board 5 Screw off the fixing screws to remove the evaporator 4 screws 1 screw...
Страница 155: ...152 5 Remove the four fixing screws of the fan motor then remove the motor 5...
Страница 168: ...165 6 Remove the grounding screw 7 Remove the Wires 1 2 3 or L1 L2 S Then remove the electronic control box 5 7...