Light Commercial R410A on-off
DM17-01.01.08en
175
The louver operates the same as in relevant mode.
If the machine switches mode between heating and cooling, the compressor pauses for a certain period of
time intermittently and then selects a mode based on T1-Ts.
If the setting temperature is modified, the machine selects a new running function.
1.3.5 Dehumidifier Mode
1.3.5.1 Indoor fan speed is fixed at low and cannot be changed
1.3.5.2 All protections are activated and operate the same as they do in cooling mode.
1.3.5.3 The louver operates the same as in cooling mode.
1.3.6 Timer function
1.3.6.1 The timing range is 24 hours.
1.3.6.2 Timer On. The machine turns on automatically at the preset time.
1.3.6.3 Timer Off. The machine turns off automatically at the preset time.
1.3.6.4 Timer On/Off. The machine turns on automatically at the preset On Time, and then turns off
automatically at the preset Off Time.
1.3.6.5 Timer Off/On. The machine turns on automatically at the preset Off Time and then turns off
automatically at the preset On Time.
1.3.6.6 The timer does not change the unit operation mode. If the unit is off now, it does not start up
immediately after the “timer off” function is set. When the setting time is reached, the timer LED switches ioff
and the unit running mode remains unchanged.
1.3.6.7 The timer uses relative time, not clock time.
1.3.7 Sleep function
1.3.7.1 The sleep function is available in cooling, heating, or auto mode.
1.3.7.2. The operational process for sleep mode is as follows:
When cooling, the temperature rises 1
℃
(to not higher than 30
℃
) every hour. After 2 hours, the
temperature stops rising and the indoor fan is fixed to auto speed.
When heating, the temperature decreases 1
℃
(to not lower than 17
℃
) every hour. After 2 hours, the
temperature stops decreasing and the indoor fan is fixed at auto speed. Anti-cold wind function takes priority.
1.3.7.3 The operating time for sleep mode is 7 hours, after which, the unit exits this mode and switches off.
1.3.7.4 The timer setting is available in this mode.
1.3.8 Auto-Restart function
The indoor unit has an auto-restart module that allows the unit to restart automatically. The module
automatically stores the current settings (not including the Swing setting) and, in the case of a sudden power
failure, will restore those setting automatically within 3 minutes after power returns.
1.3.9 Drain Pump Control (For Duct and Cassette)
Use the water-level switch to control drain pump.
The system checks the water level every 5 seconds.
----When the A/C operates in cooling (including auto cooling) or forced cooling mode, the pump begins
running immediately and continuously until cooling stops.
Содержание MUE-36HRN1-R1
Страница 13: ...Light Commercial R410A on off DM17 01 01 08en 13 Dimensions 3...
Страница 14: ...DM17 01 01 08en Light Commercial R410A on off 14 Service Space 4...
Страница 18: ...DM17 01 01 08en Light Commercial R410A on off 18 Wiring Diagrams 7 MCA3 12HRN1 Q1 MCA3 18HRN1 Q1...
Страница 22: ...DM17 01 01 08en Light Commercial R410A on off 22 Field Wiring 11...
Страница 29: ...Light Commercial R410A on off DM17 01 01 08en 29 4 Service Space 1000mm 1000mm 1000mm 1000m m...
Страница 35: ...Light Commercial R410A on off DM17 01 01 08en 35 6 Wiring Diagrams MCD 18HRN1 Q1 MCD 24HRN1 Q1...
Страница 36: ...DM17 01 01 08en Light Commercial R410A on off 36 MCD 36HRN1 R1...
Страница 37: ...Light Commercial R410A on off DM17 01 01 08en 37 MCD 48HRN1 R MCD 60HRN1 R...
Страница 41: ...Light Commercial R410A on off DM17 01 01 08en 41 10 Field Wiring MCD 18HRN1 Q1 MCD 24HRN1 Q1...
Страница 42: ...DM17 01 01 08en Light Commercial R410A on off 42 MCD 36HRN1 R1 MCD 48HRN1 R MCD 60HRN1 R...
Страница 55: ...Light Commercial R410A on off DM17 01 01 08en 55 6 Wiring Diagrams MTB 18HWN1 Q1 MTB 24HWN1 Q1...
Страница 56: ...DM17 01 01 08en Light Commercial R410A on off 56 MTI 36HWN1 R1 MTB 48HWN1 R MTB 60HWN1 R...
Страница 63: ...Light Commercial R410A on off DM17 01 01 08en 63 11 Field Wiring MTB 18HWN1 Q1 MTB 24HWN1 Q1...
Страница 64: ...DM17 01 01 08en Light Commercial R410A on off 64 MTI 36HWN1 R MTB 48HWN1 R MTB 60HWN1 R...
Страница 76: ...DM17 01 01 08en Light Commercial R410A on off 76 6 Wiring Diagrams MHG 24HWN1 Q1...
Страница 77: ...Light Commercial R410A on off DM17 01 01 08en 77 MHG 36HWN1 R1...
Страница 78: ...DM17 01 01 08en Light Commercial R410A on off 78 MHG 48HWN1 R...
Страница 79: ...Light Commercial R410A on off DM17 01 01 08en 79 MHG 60HWN1 R...
Страница 84: ...DM17 01 01 08en Light Commercial R410A on off 84 11 Field Wiring MHG 24HWN1 Q1 MHG 36HWN1 R1...
Страница 85: ...Light Commercial R410A on off DM17 01 01 08en 85 MHG 48HWN1 R MHG 60HWN1 R...
Страница 91: ...Light Commercial R410A on off DM17 01 01 08en 91 4 Service Space...
Страница 98: ...DM17 01 01 08en Light Commercial R410A on off 98 6 Wiring Diagram MUE 12HRN1 Q1 MUE 18HRN1 Q1 MUE 24HRN1 Q1...
Страница 99: ...Light Commercial R410A on off DM17 01 01 08en 99 MUE 36HRN1 R1 MUE 48HRN1 R MUE 60HRN1 R...
Страница 103: ...Light Commercial R410A on off DM17 01 01 08en 103 10 Field Wiring MUE 12HRN1 Q1 MUE 18HRN1 Q1 MUE 24HRN1 Q1...
Страница 104: ...DM17 01 01 08en Light Commercial R410A on off 104 MUE 36HRN1 R1 MUE 48HRN1 R MUE 60HRN1 R...
Страница 109: ...Light Commercial R410A on off DM17 01 01 08en 109 3 Dimensions Dimension Model W mm D mm H mm 24 500 315 1700 H W D...
Страница 110: ...DM17 01 01 08en Light Commercial R410A on off 110 4 Service Space...
Страница 112: ...DM17 01 01 08en Light Commercial R410A on off 112 6 Wiring Diagrams MFM 24ARN1 Q...
Страница 124: ...DM17 01 01 08en Light Commercial R410A on off 124 5 Wiring Diagrams MOBA30U 12HN1 Q MOBA30U 18HN1 Q MOCA30U 24HN1 Q...
Страница 125: ...Light Commercial R410A on off DM17 01 01 08en 125 MOD31U 36HN1 R MOU 48HN1 R...
Страница 126: ...DM17 01 01 08en Light Commercial R410A on off 126 MOUA 60HN1 R...
Страница 178: ...DM17 01 01 08en Light Commercial R410A on off 178 2 1 5 Display board of floor standing...