DM17-01.01.08en
Light Commercial R410A on-off
158
6. Drainage pipe installation
Install the drainage pipe as shown below and take measures against condensation. Improperly installation
could lead to leakage and eventually wet furniture and belongings.
6.1 Installation principle
Ensure at least 1/100 slope of the drainage pipe
Adopt suitable pipe diameter
Adopt nearby condensate water discharge
6.2 Key points of drainage water pipe installation
6.2.1 Considering the pipeline route and elevation
Before installing condensate water pipeline, determine its route and elevation to avoid intersection with
other pipelines and ensure slope is straight.
6.2.2 Drainage pipe selection
The drainage pipe diameter shall not small than the drain hose of indoor unit
According to the water flowrate and drainage pipe slope to choose the suitable pipe, the water flowrate
is decided by the capacity of indoor unit.
Relationship between water flowrate and capacity of indoor unit
Capacity (x1000Btu)
Water flowrate (l/h)
12
2.4
18
4
24
6
36
8
48
12
60
14
According to the above table to calculate the total water flowrate for the confluence pipe selection.
For horizontal drainage pipe
(The following table is for reference)
PVC pipe
Reference value of inner
diameter of pipe (mm)
Allowable maximum water flowrate (l/h)
Remark
Slope 1/50
Slope 1/100
PVC25
20
39
27
For branch pipe
PVC32
25
70
50
PVC40
31
125
88
Could be used for confluence pipe
PVC50
40
247
175
PVC63
51
473
334
Attention: Adopt PVC40 or bigger pipe to be the main pipe.
For Vertical drainage pipe
(The following table is for reference)
PVC pipe
Reference value of inner
diameter of pipe (mm)
Allowable maximum water flowrate (l/h)
Remark
PVC25
20
220
For branch pipe
PVC32
25
410
PVC40
31
730
Could be used for confluence pipe
PVC50
40
1440
PVC63
51
2760
PVC75
67
5710
PVC90
77
8280
Attention: Adopt PVC40 or bigger pipe to be the main pipe.
6.2.3 Individual design of drainage pipe system
The drainage pipe of air conditioner shall be installed separately with other sewage pipe, rainwater pipe
and drainage pipe in building.
The drainage pipe of the indoor unit with water pump should be apart from the one without water pump.
Содержание MUE-36HRN1-R1
Страница 13: ...Light Commercial R410A on off DM17 01 01 08en 13 Dimensions 3...
Страница 14: ...DM17 01 01 08en Light Commercial R410A on off 14 Service Space 4...
Страница 18: ...DM17 01 01 08en Light Commercial R410A on off 18 Wiring Diagrams 7 MCA3 12HRN1 Q1 MCA3 18HRN1 Q1...
Страница 22: ...DM17 01 01 08en Light Commercial R410A on off 22 Field Wiring 11...
Страница 29: ...Light Commercial R410A on off DM17 01 01 08en 29 4 Service Space 1000mm 1000mm 1000mm 1000m m...
Страница 35: ...Light Commercial R410A on off DM17 01 01 08en 35 6 Wiring Diagrams MCD 18HRN1 Q1 MCD 24HRN1 Q1...
Страница 36: ...DM17 01 01 08en Light Commercial R410A on off 36 MCD 36HRN1 R1...
Страница 37: ...Light Commercial R410A on off DM17 01 01 08en 37 MCD 48HRN1 R MCD 60HRN1 R...
Страница 41: ...Light Commercial R410A on off DM17 01 01 08en 41 10 Field Wiring MCD 18HRN1 Q1 MCD 24HRN1 Q1...
Страница 42: ...DM17 01 01 08en Light Commercial R410A on off 42 MCD 36HRN1 R1 MCD 48HRN1 R MCD 60HRN1 R...
Страница 55: ...Light Commercial R410A on off DM17 01 01 08en 55 6 Wiring Diagrams MTB 18HWN1 Q1 MTB 24HWN1 Q1...
Страница 56: ...DM17 01 01 08en Light Commercial R410A on off 56 MTI 36HWN1 R1 MTB 48HWN1 R MTB 60HWN1 R...
Страница 63: ...Light Commercial R410A on off DM17 01 01 08en 63 11 Field Wiring MTB 18HWN1 Q1 MTB 24HWN1 Q1...
Страница 64: ...DM17 01 01 08en Light Commercial R410A on off 64 MTI 36HWN1 R MTB 48HWN1 R MTB 60HWN1 R...
Страница 76: ...DM17 01 01 08en Light Commercial R410A on off 76 6 Wiring Diagrams MHG 24HWN1 Q1...
Страница 77: ...Light Commercial R410A on off DM17 01 01 08en 77 MHG 36HWN1 R1...
Страница 78: ...DM17 01 01 08en Light Commercial R410A on off 78 MHG 48HWN1 R...
Страница 79: ...Light Commercial R410A on off DM17 01 01 08en 79 MHG 60HWN1 R...
Страница 84: ...DM17 01 01 08en Light Commercial R410A on off 84 11 Field Wiring MHG 24HWN1 Q1 MHG 36HWN1 R1...
Страница 85: ...Light Commercial R410A on off DM17 01 01 08en 85 MHG 48HWN1 R MHG 60HWN1 R...
Страница 91: ...Light Commercial R410A on off DM17 01 01 08en 91 4 Service Space...
Страница 98: ...DM17 01 01 08en Light Commercial R410A on off 98 6 Wiring Diagram MUE 12HRN1 Q1 MUE 18HRN1 Q1 MUE 24HRN1 Q1...
Страница 99: ...Light Commercial R410A on off DM17 01 01 08en 99 MUE 36HRN1 R1 MUE 48HRN1 R MUE 60HRN1 R...
Страница 103: ...Light Commercial R410A on off DM17 01 01 08en 103 10 Field Wiring MUE 12HRN1 Q1 MUE 18HRN1 Q1 MUE 24HRN1 Q1...
Страница 104: ...DM17 01 01 08en Light Commercial R410A on off 104 MUE 36HRN1 R1 MUE 48HRN1 R MUE 60HRN1 R...
Страница 109: ...Light Commercial R410A on off DM17 01 01 08en 109 3 Dimensions Dimension Model W mm D mm H mm 24 500 315 1700 H W D...
Страница 110: ...DM17 01 01 08en Light Commercial R410A on off 110 4 Service Space...
Страница 112: ...DM17 01 01 08en Light Commercial R410A on off 112 6 Wiring Diagrams MFM 24ARN1 Q...
Страница 124: ...DM17 01 01 08en Light Commercial R410A on off 124 5 Wiring Diagrams MOBA30U 12HN1 Q MOBA30U 18HN1 Q MOCA30U 24HN1 Q...
Страница 125: ...Light Commercial R410A on off DM17 01 01 08en 125 MOD31U 36HN1 R MOU 48HN1 R...
Страница 126: ...DM17 01 01 08en Light Commercial R410A on off 126 MOUA 60HN1 R...
Страница 178: ...DM17 01 01 08en Light Commercial R410A on off 178 2 1 5 Display board of floor standing...