Service manual
37
11.10.3 All protections of remote control cooling are available at forced cooling operation
11.10.4 Forced Auto function
Select forced auto function with the forced auto button or the switch.
In forced auto status the A/C operates at remote control mode with a set temp. of 24
℃
11.11 Sleep mode
11.11.1 The sleep function is available at cooling, heating or auto mode
11.11.2 Cooling:
The set temperature rise 1
℃
per hour. Two hours later, the set temperature will maintain as a constant and the fan speed is kept at
low speed.
The total time is 7 hours, after 7 hours the unit stops
11.11.3 Heating:
The set temperature decrease 1
℃
per hour. Two hours later, the set temperature will maintain as a constant and the air
circulation is kept at low speed (Cold air proof function takes precedence over all).
The total time is 7 hours, after 7 hours the unit stops
11.11.4 Auto:
After an hour running under economic mode, the set temp will rise 1
℃
,if it is under cooling mode; the set temp will decrease 1
℃
,if it is
under heating mode; the set temp will be changeless, if it is under fan-only mode; the condition will be the same after the air conditioner
running under economic mode after 2 hours, and during the next time the set temp do not change. The total time is 7 hours, after 7
hours the unit stops.
11.12 Auto restart function
In case of a sudden power failure, this function automatically sets the unit to previous settings before the power failure when
power returns
All manuals and user guides at all-guides.com
Содержание MSQ-07CR
Страница 9: ...Service manual 6 3 2 Outdoor unit MSQ 07 09C H R All manuals and user guides at all guides com...
Страница 10: ...Service manual 7 MSQ 12C H R All manuals and user guides at all guides com...
Страница 17: ...Service manual 14 MSQ3 07HR MSQ3 09HR MSQ3 12HR MSQ3 12HR All manuals and user guides at all guides com...
Страница 18: ...Service manual 15 All manuals and user guides at all guides com...