PROBLEM

POSSIBLE CAUSE

REMEDY

No power

Check voltage at electrical outlet. Correct if none.

Transformer (Discharge
transformer before testing)

Check resistance between the two input/output lines on transformer.
Replace the transformer if either of the input/output is open or the
transformer is damaged.

Battery failure

Check the voltage of battery. Replace batteries if the voltage is lower
than 2.3V.

No power

Check voltage at electrical outlet. Correct if none.

Power supply cord

Check voltage at the power cord termianl on Main board. Replace the
power cord if none.

Transformer (Discharge
transformer before testing)

Check resistance between the two input/output lines on transformer.
Replace the transformer if either of the input/output is open or the
transformer is damaged.

Wire disconnected or connection
loose

Connect wire. Refer to wiring diagram for termianl identification. Repair
or replace losse terminal.

Main board failure

Select fan speed and Check the voltage of CN11 on main board. Replace
the main board if no voltage.

Capacitor (Discharge capacitor
before testing)

Test capacitor.
Replace if not /-10% of manufacture's rating. Replace if shorted,
open or damaged.

Will not rotate

Fan blower hitting scroll. Realign assembly.                                 Check
fan motor bearings. Replace the motor if motor shaft don't rotate.
Check voltage. Call an electrician if not within limits.
Test capacitor.
Replace if not /-10% of manufacture's rating.
Check bearings. Replace the motor if the fan blade cannot rotate freely.
Pay attention to any change from high speed to low speed. Replace the
motor if the speed does not change.

Fans

Replace the fans if cracked, out of balance, or partially missing.

Loose screws

Tighten them.

Worn bearings

Replace the motor if knocking sounds continue when running or loose,
or the motor hums or noise appears to be internal while running.

Copper tubing

Remove the cabinet and carefully rearrange tubing not to contact
cabinet, compressor, etc.

Discharging pipe

Check outdoor wind discharging pipe, the tie-in, the air discharger.
Correct if any problem. Replace if damaged.

Parts loosen

Tighten them.

Compressor

Replace after checked failure.

The ground is not level or not flat
enough

Place the unit on a flat, level ground.

Voltage

Check voltage. Call an electrician if not within limits.

Wiring

Check the wire connections, if loose, repair or replace the terminal. If
wires are off, refer to wiring diagram for identification, and replace.
Check wire locations. If not per wiring diagram, correct.

Main board failure

Check voltage RL4 of main board. Replace the main board if open.

Capacitor (Discharge capacitor
before testing)

Check the capacitor.
Replace if not /-10% of manufacturers rating. Replace if shorted,
open, or damaged.

Room temp sensor

Check the temperature setting if not at the coolest (in cooling mode) or
the heatest (in heating mode). Set it if not.

Pipe temp sensor

Check whether the evaporator is blocked. Check the pipe temp sensor
and replace if open circuit.

Water depth controller switch

Check whether the water tank is in correct postiong. Replace the water
depth controller switch if checked failure.

Over-current protector

Replace after checked failure.

Compressor

Check the compressor for open circuit or ground. If open or grounded,
replace the compressor.

PROBLEM SOLVING

Check the voltage of CN7 on main board. Replace the display board after
checked faulty else replace the main board.

Fan motor will not run.

Remote control failure.

Display board or main PCB failure

No display on panel or
any one of the button
failure.

11

Revolves on overload.

Fan motor runs
intermittently

Fan motor noise.

Compressor will not run
while fan motor runs.

Excessive noise.

Содержание MPA-08CE

Страница 1: ...Service Manual Mobile type GD Midea Refrigeration Equipment Co Ltd Model applied MPA 08CE MPA 08CR MPA 08EE MPA 08ER...

Страница 2: ...m The refrigerant is charged at the factory Be sure to read the safety precautions prior to servicing the unit 1 1 SAFETY PRECAUTIONS 1 When servicing the unit set the POWER SWITCH to OFF and unplug t...

Страница 3: ...luminium Hydrophilic aluminium e Tube outside dia and type mm 7 94x0 35 innergroove tube 7 94x0 35 innergroove tube f Coil length x height x width mm 274x264x38 1 274x264x38 1 g Number of circuits 1 1...

Страница 4: ...Fin type code Hydrophilic aluminium Hydrophilic aluminium e Tube outside dia and type mm 7 94x0 35 innergroove tube 7 94x0 35 innergroove tube f Coil length x height x width mm 274x264x38 1 274x264x38...

Страница 5: ...I 6 Remote display 7 Mode button 8 9 Fan button A B C Swing button D Up button E Clock button F Reset button G Lock button H I Timer on button Timer off button Display the situation of operation setti...

Страница 6: ...COVER DRAIN TANK 2 INSTALLATION Installation Accessories Description Quantity Flexible exhaust hose with adapters 3 set 1 3 stretches from 19 50cm up to 78 200cm 2 4 Window exhaust adapter flat mouth...

Страница 7: ...nside the cabinet otherwise the unit will not operate 5 To turn the unit on press the I O key On Off Switch Water Tank Safety Feature This unit is equipped with a fail safe switch mechanism which prev...

Страница 8: ...2 1 THE SETTING OF AUTO SWING When the air conditioner is operating press the SWING key at any mode to start the auto swing 3 2 2 OFF TIMER Set the OFF TIMER at any mode when the air condition is oper...

Страница 9: ...minutes re starting the machine after the compressor is stopped needs to wait for 3 minutes 3 2 5 5 CURRENT PROTECTION FOR COMPRESSOR During operation if over current lasts for 3 seconds the compresso...

Страница 10: ...Check fan motor capacitor Is the voltage of CN11 on main board correct Replace main board Yes No Replace fan motor Yes Check Whether the evaporator or condenser is blocked Check compressor capacitor C...

Страница 11: ...eck fan speed Yes No Replace main board Check air filter Is temperature of suction pipe on compressor higher o than 19 C No Replace compressor Check leakage repair and recharge refrigerant Yes Check r...

Страница 12: ...f knocking sounds continue when running or loose or the motor hums or noise appears to be internal while running Copper tubing Remove the cabinet and carefully rearrange tubing not to contact cabinet...

Страница 13: ...maged Water depth controller switch Check whether the water tank is in correct postiong Replace the water depth controller switch if checked failure Main board Check and replace the main board after c...

Страница 14: ...13 4 SCHEMATIC DIAGRAM 4 1 CIRCUIT DIAGRAM For Model MPA 08CE and MPA 08CR For Model MPA 08EE and MPA 08ER...

Отзывы: