Oasis On-off
DM12-01.01.09en
18
Service
manual
MS11M-24HRN1 / MO11M-24HN1
Cooling
Cooling
Outdoor conditions (DB)
Indoor Conditions
(kW)
18ºC
21ºC
28ºC
35ºC
43ºC
TC
7.59
7.24
6.89
6.54
6.26
21/15ºC DB/WB
SC
5.47
5.36
5.30
5.23
5.26
Input
2.40
2.49
2.70
2.82
2.91
TC
7.73
7.45
7.10
6.75
6.33
24/17ºC DB/WB
SC
5.65
5.59
5.54
5.47
5.31
Input
2.43
2.64
2.82
2.94
3.09
TC
7.87
7.59
7.24
7.03
6.54
27/19ºC DB/WB
SC
5.67
5.62
5.58
5.48
5.36
Input
2.52
2.70
2.85
3.00
3.15
TC
8.01
7.73
7.45
7.31
6.75
32/23ºC DB/WB
SC
6.65
6.57
6.48
6.43
6.28
Input
2.70
2.82
2.94
3.15
3.27
Heating
Heating Outdoor
conditions
Indoor Conditions
(DB) (kW)
24/18ºC
DB/WB
7/6ºC
DB/WB
2/1ºC
DB/WB
-5/-6ºC
DB/WB
-7/-8ºC
DB/WB
15ºC
TC
9.53 7.70 6.30 5.72 5.35
Input
3.77 3.25 2.79 2.62 2.48
20ºC
TC 9.24
7.33
5.94 5.57 5.13
Input 4.12
3.49
3.07 2.83 2.65
27ºC
TC
8.65 6.89 5.57 5.42 4.84
Input
4.36 3.77 3.32 3.07 2.86
Remark:
TC: Total capacity; kW
SC: Sensible heat capacity; kW
Input: Input power; kW