MLCAC-UTSM-2010-10
Water Drainage
Installation
101
4. Water Drainage
4.1 Gradient and Supporting
1). Keep the drainpipe sloping downwards at a gradient of at least 1/50. Keep the drainpipe as short as possible and eliminate the air bubble.
2). The horizontal drainpipe should be short. When the pipe is too long, a prop stand must be installed to keep the gradient of 1/50 and
prevent bending. Refer to the following table for the specification of the prop stand.
Diameter
Distance between the prop stands
Hard PVC pipe
25~40mm
1.5~2m
3). Precautions
The diameter of drainpipe should meet the drainage requirement at least.
the drainpipe should be heat-insulated to prevent atomization.
Drainpipe should be installed before installing indoor unit. After powering on, there is some water in water-receiver plate. Please check if the
drain pump can operate correctly.
All connection should be firm.
Wipe color on PVC pipe to note connection.
Climbing, horizontal and bending conditions are prohibited.
The dimension of drainpipe can’t less than the connecting dimension of indoor drainpipe.
Heat-insulation should be done well to prevent condensation.
Indoor units with different drainage type can’t share one convergent drainpipe.
4.2 Drainpipe Trap
1). If the pressure at the connection of the drainpipe is negative, it needs to design drainpipe trap.
2). Every indoor unit needs one drainpipe trap.
3). A plug should be designed to do cleaning.
Plug
5
0
cm
5
0
c
m
4.3 Upwards drainage (drain pump)
For Four-way cassette(compact)
Содержание MLCAC-UTSM-2010-10
Страница 1: ...MIDEA LCAC 50Hz R410A DC Inverter Service Manual 2011 ...
Страница 2: ......
Страница 4: ......
Страница 16: ...Service Space MLCAC UTSM 2010 10 12 Four way Cassette Type 3 Service Space ...
Страница 17: ...MLCAC UTSM 2010 10 Wiring Diagrams Four way Cassette Type 13 4 Wiring Diagrams MCC 36HRDN1 MCC 48HRDN1 ...
Страница 21: ...MLCAC UTSM 2010 10 The Specification of Power Four way Cassette Type 17 9 The Specification of Power ...
Страница 22: ...Field Wiring MLCAC UTSM 2010 10 18 Four way Cassette Type 10 Field Wiring Wiring chart ...
Страница 23: ...MLCAC UTSM 2010 10 Field Wiring Four way Cassette Type 19 ...
Страница 32: ...The Specification of Power MLCAC UTSM 2010 10 28 Duct Type 9 The Specification of Power ...
Страница 33: ...MLCAC UTSM 2010 10 Field Wiring Duct Type 29 10 Field Wiring ...
Страница 34: ...Field Wiring MLCAC UTSM 2010 10 30 Duct Type Air conditioner link circuit ...
Страница 37: ......
Страница 40: ...Service Space MLCAC UTSM 2010 10 58 Ceiling Floor Type 3 Service Space ...
Страница 41: ...MLCAC UTSM 2010 10 Wiring Diagrams Ceiling Floor Type 59 4 Wiring Diagrams MUB 36HRDN1 MUB 48HRDN1 ...
Страница 46: ...The Specification of Power MLCAC UTSM 2010 10 64 Ceiling Floor Type 9 The Specification of Power ...
Страница 47: ...MLCAC UTSM 2010 10 Field Wiring Ceiling Floor Type 65 10 Field Wiring ...
Страница 48: ...Field Wiring MLCAC UTSM 2010 10 66 Ceiling Floor Type ...
Страница 51: ...MLCAC UTSM 2010 10 Service Space Outdoor Units 69 2 Service Space ...
Страница 53: ...MLCAC UTSM 2010 10 Wiring Diagrams Outdoor Units 71 4 Wiring Diagrams MOUB 36HDN1 Q MOU 48HDN1 MOUB 36HDN1 R ...
Страница 54: ...Wiring Diagrams MLCAC UTSM 2010 10 72 Outdoor Units MOUB 48HDN1 R ...
Страница 60: ...Troubleshooting MLCAC UTSM 2010 10 78 Outdoor Units For Duct type ...
Страница 89: ...MLCAC UTSM 2010 10 Control Control 107 Part 5 Control 1 Controller 108 ...