background image

4. Refrigerant Piping Installation

4.1  Length  and  Drop  Height  Requirements  for  the  Piping 

Connections to the Indoor and Outdoor Units

The length and drop height requirements for the refrigerant piping are different 
for different indoor and outdoor units. Refer to the installation manual of the 
outdoor unit.

4.2 Piping Material and Size

1.  Piping material: Copper pipes for air handling.
2.  Piping  size:  Choose  and  purchase  copper  pipes  that  correspond  to  the 

length and size calculated for the selected model in the installation manual 
of the outdoor unit and your actual project requirements.

4.3 Piping Layout

1.  Seal the two ends of the piping properly before you connect the indoor and 

outdoor  piping.  Once  unsealed,  connect  the  piping  of  the  indoor  and 
outdoor units as quickly as possible to prevent dust or other debris from 
entering the piping system via the unsealed ends, as this may cause the 
system to malfunction.

2.  If the piping needs to go through walls, drill the opening in the wall, and 

place accessories like casings and covers for the opening properly.

3.  Place the refrigerant connecting piping and the communication wiring for the 

indoor and outdoor units together, and bundle them tightly to make sure air 
does not enter and condensate to form water that may leak from the system.

4.  Insert the bundled piping and wiring from outside the room through the wall 

opening  into  the  room.  Be  careful  when  you  lay  out  the  piping.  Do  not 
damage the piping.

4.4 Piping Installation

  Refer to the installation manual attached with the outdoor unit on installation 

of the refrigerant piping for the outdoor unit.

  All gas and liquid piping must be properly insulated; otherwise, this may cause 

water to leak. Use heat insulation materials that can withstand high tempera-
tures above 120°C to insulate the gas pipes. In addition, the insulation of the 
refrigerant piping should be reinforced (20 mm or thicker) in situations where 
there is high temperature and/or high humidity (when part of refrigerant piping 
part is higher than 30°C or when the humidity exceeds RH80%). Otherwise, 
the surface of the heat insulation material may be exposed.

  Before the works are carried out, verify that the refrigerant is R410A. If the 

wrong refrigerant is used, the unit may malfunction.

  Other than the specified refrigerant, do not let air or other gases enter the 

refrigeration circuit.

  If the refrigerant leaks during installation, make sure you fully ventilate the room.

  Use  two  wrenches  when  you  install  or  dismantle  the  piping,  a  common 

wrench and a torque wrench. See Figure 4.1.

 

 

  Apply  the  appropriate  tightening  torque  according  to  the  installation 

conditions. Excessive torque will damage the socket cap, and the cap will 
not be tight if you apply insufficient torque, leading to leakages.

4.5 Air Tightness Test

Carry out the air tightness test on the system according to the instructions in the 
installation manual of the outdoor unit.

4.7 Vacuum

Create a vacuum in the system according to the instructions in the installation 
manual of the outdoor unit.

4.8 Refrigerant

Charge  the  system  with  refrigerant  according  to  the  instructions  in  the 
installation manual of the outdoor unit.

 

 

4.6 Heat Insulation Treatment for Gas-Liquid Piping Connections 

for the Indoor Unit

  The heat insulation treatment is carried out on the piping at the gas and liquid 

sides of the indoor unit respectively.

a.  The piping on the gas side must use heat insulation material that can 

withstand temperatures of 120°C and more.

b.  For the piping connections of the indoor unit, use the insulation casing 

for copper pipes (accessory 6) to carry out the insulation treatment, 
and close all gaps.

Unit 

body

Attached insulation 

heat pump belt

On-site 

piping side

Face upwards

Figure 4.5

Figure 4.1

Torque wrench
Pipe socket cap

Pipe fittings

Normal wrench

  Slot the refrigerant piping into the brass nut (accessory 13), and expand the 

pipe socket. Refer to the following table for the size of the pipe socket and 
the appropriate tightening torque.

Figure 4.2

External diameter

 (mm)

Tightening 

torque

Figure 4.3

Apply refrigerant oil

  Before the socket cap is installed on the pipe socket, apply some refrigerant 

oil on the socket (both inside and outside), and then rotate it three or four 
times before you tighten the cap. See Figure 4.3.

Precautions to take when welding the refrigerant pipes

 

Before you weld the refrigerant pipes, fill the pipes with nitrogen first to 
discharge the air in the pipes. If no nitrogen is filled during welding, a large 
amount of oxide film will form inside the piping which may cause the air 
conditioning system to malfunction.

 

Welding can be carried out on the refrigerant pipes when the nitrogen gas 
has been replaced or refilled.

 

When the pipe is filled with nitrogen during welding, the nitrogen must be 
reduced to 0.02 MPa using the pressure release valve. See Figure 4.4.

Figure 4.4

 

The Air Tightness Test helps to ensure that the air and liquid cut-off 
valves of the outdoor unit are all closed (maintain the factory defaults).

 

 

 

 

For the vacuum, make sure that the air and liquid cut-off valves of the 
outdoor unit are all closed (maintain the factory status).

 

 

 

Caution

Caution

R0.4~0.8

A

45°±  2

90°± 4

Flared opening

diameter (A)

Flared opening

Φ

6.35

14.2-17.2N·m

8.3-8.7mm

Φ

9.53

32.7-39.9N·m

12-12.4mm

Φ

12.7

49.5-60.3N·m

15.4-15.8mm

Φ

15.9

61.8-75.4N·m

18.6-19mm

Φ

19.1

97.2-118.6N·m

22.9-23.3mm

Caution

Figure 4.4

1 Copper piping
2 Section being brazed
3 Nitrogen connection
4 Hand valve
5 Pressure-reducing valve
6 Nitrogen

9

Содержание MI2-100Q4DHN1

Страница 1: ...ion DC VRF indoor unit Installation and Operation Manual Original instructions Thank you very much for purchasing our air conditioner Before using your air conditioner please read this manual carefully and keep it for future reference ...

Страница 2: ......

Страница 3: ...s and wires Improper wiring and installation may cause a fire Make sure the power cord communication and controller wiring are straight and level when you are working on the connections and the cover on the electric box is tight If the electric box is not closed properly it may lead to electric shock fire or overheating of electrical components If the refrigerant leaks during installation open the...

Страница 4: ...ontent the mechanical parts will experience accelerated ageing which will severely compromise the service life of the unit 5 Where there are major voltage fluctuations Operating the unit using a power supply system that has large voltage fluctuations will reduce the service life of the electronic components and cause the unit s controller system to malfunction 6 Where there is a risk of leakage of...

Страница 5: ...39 mm inner diameter 32 mm The inner diameter is based on the diameter of the copper and PVC pipes The thickness of the pipe casing is 10 mm or more Increase the thickness of the casing 20 mm or thicker when the temperature exceeds 30 C or the humidity exceeds RH80 To purchase based on actual project requirements Use to connect indoor refrigerant piping Use to discharge condensed water from the in...

Страница 6: ...ections for the installation site See Figure 2 3 for the schematic on the direction of airflow If part of the air vent must be blocked you may insert an air baffle at the vent of the unit body to block the air flow See Figure 2 4 2 Choosing an Installation Site Figure 2 1 Panel Ceiling 910 mm ceiling hole position Air inlet Air outlet Air outlet Floor Connect to water piping outlet Figure 2 2 Conn...

Страница 7: ...or mounting and drill four Φ12mm X 50 55 mm holes Then embed and set up the expansion hook anchors purchased accessory 4 in these holes See Figure 3 2 During the installation of the hooks purchased accessory 5 make sure that the concave portion of the hanger corresponds to that of the expansion hook anchors Determine the appropriate hook length for installation based on the ceiling s height Remove...

Страница 8: ... Buffers Dimensions of unit ϕ75 fresh air vent Refrigerant piping vent liquid side C Refrigerant piping vent gas side D ϕ32 outer diameter of water discharge pipe Figure 3 10 Figure 3 11 Mounting hooks Master air conditioner Ceiling Panel Hex nut to adjust level All the figures in this manual are for illustration purposes only The actual air conditioner you purchased may not have the same appearan...

Страница 9: ...ective casing to wrap the connection terminals and use a reliable fixture to secure and strengthen the safety isolation of the terminals 4 Adjust the four panel hook screws see Figure 3 15 c to keep the panel level and lift it evenly up to the ceiling 5 Adjust the panel slightly in the d direction see Figure 3 15 d so that the centre of the panel aligns with the centre of the opening of the ceilin...

Страница 10: ... for the schematic on the installation dimensions of the air ducts Figure 3 22 See Figure 3 23 for the schematic on the air duct installation Figure 3 23 If only one air duct is connected The air volume in the air duct for the 5 6 8 0 kW model is about 300 360 m3 h The air volume in the air duct for the 9 0 14 0 kW models is about 400 640 m3 h Length of the air duct should not exceed 2 m If two ai...

Страница 11: ...ssive torque will damage the socket cap and the cap will not be tight if you apply insufficient torque leading to leakages 4 5 Air Tightness Test Carry out the air tightness test on the system according to the instructions in the installation manual of the outdoor unit 4 7 Vacuum Create a vacuum in the system according to the instructions in the installation manual of the outdoor unit 4 8 Refriger...

Страница 12: ... plugged to prevent water from leaking 5 Water Discharge Piping Installation 5 1 Water Discharge Piping Installation for Indoor Unit 1 Use PVC pipes for the water discharge pipes outer diameter 37 39 mm inner diameter 32 mm Based on the actual installation circumstance users can purchase the appropriate piping length from sales agent or local after sales service centre or purchase directly from th...

Страница 13: ...connect the power cord firmly To prevent the cord from being pulled out by external force make sure it is fixed securely Figure 6 2 shows the power supply terminal of the indoor unit Refer to Tables 6 1 and 6 2 for the specifications of the power cord and communication wire A wiring capacity that is too small will cause the electrical wiring to become too hot and lead to accidents when the unit bu...

Страница 14: ...adding the build out resistor at P and Q open Indoor and outdoor units Communication wire Connecting the shielded layer of the shielded wire Connect the shielded end of the shielded wire to the electronic controller box sheet metal here Signalling line between outdoor units Outdoor unit P Q Figure 6 6 The X1 X2 D1 D2 ports on the sides of the main control board and the unidirectional communication...

Страница 15: ...unit in the system are not controlled by the centralized controller Caution The system can connect up to 64 indoor units address 0 63 at the same time Each indoor unit can only have one address DIP switch in the system The addresses of any two indoor units in the same system cannot be the same Units that have the same address may malfunction 0 1 definition of each dial code switch means 0 means 1 ...

Страница 16: ...ad to electric shocks or injuries caused by moving parts such as the unit s fan Ensure that the power supply is disconnected before any servicing or maintenance is carried out Do not touch the unit or its remote controller with wet hands as doing so can lead to electric shocks Do not allow children to play near this unit as doing so risks injury Do not insert your fingers or other objects into the...

Страница 17: ...igerant oil and other materials is adhered to Contact your local waste disposal authority for information about disposal procedures To avoid damaging the remote controller exercise caution when using it and replacing its batteries Do not place objects on top of it Do not place appliances that have naked flames under or near the unit as heat from the appliance can damage the unit Do not place the u...

Страница 18: ...an air filters inside indoor units Caution The unit performs stably in the temperature range given in above table If the indoor temperature is outside the unit s normal operating range it may stop running and display an error code 16 Cooling mode Heating mode 17 32 C DB 15 27 C DB Indoor temperature Indoor humidity a Condensation will form on the unit surface and water dripping out of the unit whe...

Страница 19: ...ell Clean the filter every two weeks when you use it regularly b If the air conditioner is positioned in a dusty place clean the filter often c Replace the filter if it is too dusty to clean the replaceable air filter is an optional fitting 1 Take out the air intake grille Push the grille switches simultaneously as indicated in Fig 13 1 Then pull down the air intake grille together with the air fi...

Страница 20: ...t will start after the intentional delay is complete Heating mode is running when the following panel lights are on operation and the DEF FAN LED indicator Cause the indoor unit activates protective measures because of the low outlet temperature Caution When the power switch is connected some energy will be consumed even if the unit is not running Disconnect the power to save energy A degree of di...

Страница 21: ...s air inlet or outlet is blocked A refrigerant leak has occurred Low heating effect Doors or windows are not completely closed Close doors and windows Arrange for a professional technician to check the following A refrigerant leak has occurred 15 2 Unit troubleshooting A power cut has occurred the power to the premises has been cut off Air flows normally but doesn t cool The unit starts or stops f...

Страница 22: ... button is pressed Check whether the MODE indicated on the display is AUTO Check whether the MODE indicated on the display is DRY A power cut has occurred the power to the premises has been cut off Check whether the timer operation has come to an end when TIMER OFF is indicated on the display Check whether the timer operation has come to an end when TIMER ON is indicated on the display Check wheth...

Страница 23: ...oil error Line loosened or broken The electronic expansion valve in stuck Outdoor unit error Water level float stuck Water level switch not connected properly Damaged main PCB Drain pump has malfunctioned 6 E 7 E b E error M O R P E E d E r o r r e t i n u r o o d t u O E E r o r r e l e v e l r e t a W FE Indoor unit has not been assigned an address Communication error between indoor and outdoor ...

Страница 24: ...16126000002969 V G ...

Страница 25: ...改前后核对和检查 B版本升级到C版本 更新整本说明书 C版本升级到D版本 P12添加线径说明 D版本升级到E版本 P12页删除图6 10 X1 X2接地 P12页6 3所有屏蔽线接地要求转移到6 3 1 E版本升级到F版本 P11表6 3 Cable for fixed wiring中的 and 为 to 图号升级 P16室内机制热温度增加下限 技术要求 双胶纸80克 黑白印刷 A4 V F V G 更改材质为80g 其余不变 ...

Отзывы: