Figure 5.1

Slope of 1/100 

or more

Figure 5.3

 

Before the test, make sure that the water discharge pipeline is smooth, and 
check that each connection is sealed properly.

 

Conduct the water discharge test in the new room before the ceiling is paved.

1.  Remove the test water cap to connect to the test water outlet, and use the 

water injection pipe to inject 2000 ml of water into the drain pan.

5.2 Water Discharge Test

Water suction pipe

Test water outlet

Body

Drain pan

Test water cap

Water injection pipe

Water discharge trench

Figure 5.2

 

Make sure all the connections in the piping system are properly sealed 

to prevent water leakages.

6.  When connecting to a long water discharge pipe, the connections must be 

covered  with  the  insulation  casing  to  prevent  the  long  pipe  from  coming 
loose.

7.  When the outlet of the water discharge pipe is higher than the pipe connec-

tion for water suction, try to keep the water discharge pipe as vertical as 
possible, and the water outlet connecting fittings will bend so that the height 
of the water discharge pipe should be within 1000 mm away from the base 
of the drain pan. Otherwise, there will be excessive water flow when the 
operation stops. See Figure 5.2.

Water discharge pipes from multiple units are connected to the main 

water discharge pipe to be discharged through the sewage pipe.

Water outlet 

pipe fittings

Main water 

outlet pipe

Slope of 

1/100 or more

Below 200 mm

All are below 1000 mm

Below 200 mm

Below 200 mm

8.  If the end of the water discharge pipe is more than 50mm above the ground 

or from the base of the water discharge slot, do not put it in the water.

2.  Connect the power supply, and set the air conditioner to operate in the cool 

mode. Check the running sound of the drainage pump, as well as whether 
water is properly drained from the water discharge outlet.

3.  Stop the air conditioner. Wait for three minutes, and then check if there is 

anything unusual. If the water discharge piping layout is not correct, the 

excessive water flow will cause the water level error and “EE” error code will 

be displayed on the display panel. There may even be water overflowing 

from the drain pan.There may even be water overflowing from the drain pan.

4.  Continue to add water until the alarm for excessive water levels is triggered. 

Check if the drainage pump drains water immediately. After three minutes, 
if the water level does not fall below the warning level, the unit will shut 
down. At this time, you need to turn off the power supply, and drain away the 
accumulated water before you can turn on the unit normally.

5.  Turn off the power supply, remove the water manually using the drainage 

plug, and put the test cap back to the original place.

 

 

The drainage plug at the bottom of the unit body is used to discharge 
accumulated  water  from  the  drain  pan  when  the  air  conditioner 
malfunctions.  When  the  air  conditioner  is  operating  normally,  make 
sure  the  drainage  plug  is  properly  plugged  to  prevent  water  from 
leaking.

5. Water Discharge Piping Installation

5.1. Water Discharge Piping Installation for Indoor Unit

1.  Use PVC pipes for the water discharge pipes (outer diameter: 37~39 mm, 

inner  diameter:  32  mm).  Based  on  the  actual  installation  circumstance, 
users can purchase the appropriate piping length from sales agent or local 
after-sales service centre, or purchase directly from the local market.

2.  Insert the water discharge pipe into the end of the water suction connecting 

pipe of the unit body, and use the ring clamp (accessory 10) to clamp the water 
discharge pipes with the insulation casing for the water outlet piping securely.

3.  Use  the  insulation  casing  for  water  discharge  piping  (accessory  9)  to 

bundle the water suction and discharge pipes of the indoor unit (especially 
the indoor portion), and use the tie for the water discharge piping (accesso-
ry 12) to bind them firmly to make sure air does not enter and condense.

4.  In  order  to  prevent  the  back-flow  of  water  into  the  interior  of  the  air 

conditioner  when  the  operation  stops,  the  water  discharge  pipe  should 
slope downwards towards the outside (drainage side) at a slope of more 
than 1/100. Make sure that the water discharge pipe does not swell or store 
water; otherwise, it will cause strange noises. See Figure 5.1.

5.  When connecting the water discharge piping, do not use force to pull the 

pipes to prevent the water suction pipe connections from coming loose. At 
the same time, set a supporting point at every 0.8~1 m to prevent the water 
discharge pipes from bending. See Figure 5.1.

Caution

50~100mm

50~100mm

50~100mm

Caution

>1.0m

0.8~1.0m

Warning

6. Electrical Wiring

  All the supplied parts, materials and electrical works must comply with local 

regulations.

  Use only copper wires.

  Use a dedicated power supply for the air-conditioners. The power voltage 

must be in line with the rated voltage.

  The electrical wiring works must be carried out by a professional technician, 

and must comply with the labels stated in the circuit diagram.

  Before the electrical connection works are carried out, turn off the power 

supply to prevent injuries caused by electric shock.

  The  external  power  supply  circuit  of  the  air  conditioner  must  include  an 

earth line, and the earth line of the power cord connecting to the indoor unit 
must be securely connected to the earth line of the external power supply.

  Leakage  protective  devices  must  be  configured  according  to  the  local 

technical standards and requirements for electrical and electronic devices.

  The fixed wiring connected must be equipped with an all-pole disconnection 

device with a minimum 3 mm contact separation.

  The distance between the power cord and signalling line must be at least 

300 mm to prevent the occurrences of electrical interference, malfunction or 
damage to electrical components. At the same time, these line must not 
come in contact with the piping and valves.

  Choose  electrical  wiring  that  conforms  to  the  corresponding  electrical 

requirements.

  Connect to the power supply only after all the wiring and connection works 

have been completed, and carefully checked to be correct.

10

Содержание MI2-100Q4DHN1

Страница 1: ...ion DC VRF indoor unit Installation and Operation Manual Original instructions Thank you very much for purchasing our air conditioner Before using your air conditioner please read this manual carefully and keep it for future reference ...

Страница 2: ......

Страница 3: ...s and wires Improper wiring and installation may cause a fire Make sure the power cord communication and controller wiring are straight and level when you are working on the connections and the cover on the electric box is tight If the electric box is not closed properly it may lead to electric shock fire or overheating of electrical components If the refrigerant leaks during installation open the...

Страница 4: ...ontent the mechanical parts will experience accelerated ageing which will severely compromise the service life of the unit 5 Where there are major voltage fluctuations Operating the unit using a power supply system that has large voltage fluctuations will reduce the service life of the electronic components and cause the unit s controller system to malfunction 6 Where there is a risk of leakage of...

Страница 5: ...39 mm inner diameter 32 mm The inner diameter is based on the diameter of the copper and PVC pipes The thickness of the pipe casing is 10 mm or more Increase the thickness of the casing 20 mm or thicker when the temperature exceeds 30 C or the humidity exceeds RH80 To purchase based on actual project requirements Use to connect indoor refrigerant piping Use to discharge condensed water from the in...

Страница 6: ...ections for the installation site See Figure 2 3 for the schematic on the direction of airflow If part of the air vent must be blocked you may insert an air baffle at the vent of the unit body to block the air flow See Figure 2 4 2 Choosing an Installation Site Figure 2 1 Panel Ceiling 910 mm ceiling hole position Air inlet Air outlet Air outlet Floor Connect to water piping outlet Figure 2 2 Conn...

Страница 7: ...or mounting and drill four Φ12mm X 50 55 mm holes Then embed and set up the expansion hook anchors purchased accessory 4 in these holes See Figure 3 2 During the installation of the hooks purchased accessory 5 make sure that the concave portion of the hanger corresponds to that of the expansion hook anchors Determine the appropriate hook length for installation based on the ceiling s height Remove...

Страница 8: ... Buffers Dimensions of unit ϕ75 fresh air vent Refrigerant piping vent liquid side C Refrigerant piping vent gas side D ϕ32 outer diameter of water discharge pipe Figure 3 10 Figure 3 11 Mounting hooks Master air conditioner Ceiling Panel Hex nut to adjust level All the figures in this manual are for illustration purposes only The actual air conditioner you purchased may not have the same appearan...

Страница 9: ...ective casing to wrap the connection terminals and use a reliable fixture to secure and strengthen the safety isolation of the terminals 4 Adjust the four panel hook screws see Figure 3 15 c to keep the panel level and lift it evenly up to the ceiling 5 Adjust the panel slightly in the d direction see Figure 3 15 d so that the centre of the panel aligns with the centre of the opening of the ceilin...

Страница 10: ... for the schematic on the installation dimensions of the air ducts Figure 3 22 See Figure 3 23 for the schematic on the air duct installation Figure 3 23 If only one air duct is connected The air volume in the air duct for the 5 6 8 0 kW model is about 300 360 m3 h The air volume in the air duct for the 9 0 14 0 kW models is about 400 640 m3 h Length of the air duct should not exceed 2 m If two ai...

Страница 11: ...ssive torque will damage the socket cap and the cap will not be tight if you apply insufficient torque leading to leakages 4 5 Air Tightness Test Carry out the air tightness test on the system according to the instructions in the installation manual of the outdoor unit 4 7 Vacuum Create a vacuum in the system according to the instructions in the installation manual of the outdoor unit 4 8 Refriger...

Страница 12: ... plugged to prevent water from leaking 5 Water Discharge Piping Installation 5 1 Water Discharge Piping Installation for Indoor Unit 1 Use PVC pipes for the water discharge pipes outer diameter 37 39 mm inner diameter 32 mm Based on the actual installation circumstance users can purchase the appropriate piping length from sales agent or local after sales service centre or purchase directly from th...

Страница 13: ...connect the power cord firmly To prevent the cord from being pulled out by external force make sure it is fixed securely Figure 6 2 shows the power supply terminal of the indoor unit Refer to Tables 6 1 and 6 2 for the specifications of the power cord and communication wire A wiring capacity that is too small will cause the electrical wiring to become too hot and lead to accidents when the unit bu...

Страница 14: ...adding the build out resistor at P and Q open Indoor and outdoor units Communication wire Connecting the shielded layer of the shielded wire Connect the shielded end of the shielded wire to the electronic controller box sheet metal here Signalling line between outdoor units Outdoor unit P Q Figure 6 6 The X1 X2 D1 D2 ports on the sides of the main control board and the unidirectional communication...

Страница 15: ...unit in the system are not controlled by the centralized controller Caution The system can connect up to 64 indoor units address 0 63 at the same time Each indoor unit can only have one address DIP switch in the system The addresses of any two indoor units in the same system cannot be the same Units that have the same address may malfunction 0 1 definition of each dial code switch means 0 means 1 ...

Страница 16: ...ad to electric shocks or injuries caused by moving parts such as the unit s fan Ensure that the power supply is disconnected before any servicing or maintenance is carried out Do not touch the unit or its remote controller with wet hands as doing so can lead to electric shocks Do not allow children to play near this unit as doing so risks injury Do not insert your fingers or other objects into the...

Страница 17: ...igerant oil and other materials is adhered to Contact your local waste disposal authority for information about disposal procedures To avoid damaging the remote controller exercise caution when using it and replacing its batteries Do not place objects on top of it Do not place appliances that have naked flames under or near the unit as heat from the appliance can damage the unit Do not place the u...

Страница 18: ...an air filters inside indoor units Caution The unit performs stably in the temperature range given in above table If the indoor temperature is outside the unit s normal operating range it may stop running and display an error code 16 Cooling mode Heating mode 17 32 C DB 15 27 C DB Indoor temperature Indoor humidity a Condensation will form on the unit surface and water dripping out of the unit whe...

Страница 19: ...ell Clean the filter every two weeks when you use it regularly b If the air conditioner is positioned in a dusty place clean the filter often c Replace the filter if it is too dusty to clean the replaceable air filter is an optional fitting 1 Take out the air intake grille Push the grille switches simultaneously as indicated in Fig 13 1 Then pull down the air intake grille together with the air fi...

Страница 20: ...t will start after the intentional delay is complete Heating mode is running when the following panel lights are on operation and the DEF FAN LED indicator Cause the indoor unit activates protective measures because of the low outlet temperature Caution When the power switch is connected some energy will be consumed even if the unit is not running Disconnect the power to save energy A degree of di...

Страница 21: ...s air inlet or outlet is blocked A refrigerant leak has occurred Low heating effect Doors or windows are not completely closed Close doors and windows Arrange for a professional technician to check the following A refrigerant leak has occurred 15 2 Unit troubleshooting A power cut has occurred the power to the premises has been cut off Air flows normally but doesn t cool The unit starts or stops f...

Страница 22: ... button is pressed Check whether the MODE indicated on the display is AUTO Check whether the MODE indicated on the display is DRY A power cut has occurred the power to the premises has been cut off Check whether the timer operation has come to an end when TIMER OFF is indicated on the display Check whether the timer operation has come to an end when TIMER ON is indicated on the display Check wheth...

Страница 23: ...oil error Line loosened or broken The electronic expansion valve in stuck Outdoor unit error Water level float stuck Water level switch not connected properly Damaged main PCB Drain pump has malfunctioned 6 E 7 E b E error M O R P E E d E r o r r e t i n u r o o d t u O E E r o r r e l e v e l r e t a W FE Indoor unit has not been assigned an address Communication error between indoor and outdoor ...

Страница 24: ...16126000002969 V G ...

Страница 25: ...改前后核对和检查 B版本升级到C版本 更新整本说明书 C版本升级到D版本 P12添加线径说明 D版本升级到E版本 P12页删除图6 10 X1 X2接地 P12页6 3所有屏蔽线接地要求转移到6 3 1 E版本升级到F版本 P11表6 3 Cable for fixed wiring中的 and 为 to 图号升级 P16室内机制热温度增加下限 技术要求 双胶纸80克 黑白印刷 A4 V F V G 更改材质为80g 其余不变 ...

Отзывы: