13. Operation Limits
Cooling operation
Outdoor ambient temperature: 10
℃
~
43
℃
Outlet water temperature: 5
℃
-17
℃
Heating operation
Outdoor ambient temperature: -15
℃
~
24
℃
Outlet water temperature: 45
℃
-50
℃
Cooling Heating
13.1 Ethylene glycol solution
Water and ethylene glycol solutions used as a thermal vector in the place of water reduce the performance
of the unit. Multiply the performance figures by the values given in the following table.
Freezing point (°C)
0
-5
-10
-15
-20
-25
Percentage of ethylene glycol in weight
0
12%
20%
28%
35%
40%
cPf
1
0.98
0.97
0.965
0.96
0.955
cQ
1
1.02
1.04
1.075
1.11
1.14
cdp
1
1.07
1.11
1.18
1.22
1.24
cPf: correction factor refrigerating capacity
cQ: correction factor flow rate
cdp: correction factor pressure drop
Note:
1. During winter leaving the unit unused, please drain water out completely from unit if no antifreeze were
charged into pipeline, or keep power on (at standby or off status) and ensure that water is contained
inside of unit.
2. When ambient temperature is lower than 5
℃
, running cooling mode must be charged antifreeze. Refers
to upper parameters for the charged volume.
13.2 Fouling factor
The performance data given refer to conditions with clean evaporator plates (fouling factor=1). For different
fouling factors, multiply the figures in the performance tables by the coefficient given in the following table.
Содержание MGA-D10/N1
Страница 13: ...MCAC ATSM 2014 01 R410A Mini Split Chiller 50Hz 13 8 Service Space...
Страница 15: ...MCAC ATSM 2014 01 R410A Mini Split Chiller 50Hz 15 10 Wiring Diagrams 10 1 MGA D10 N1...
Страница 16: ...R410A Mini Split Chiller 50Hz MCAC ATSM 2014 01 16 10 2 MGA D12 N1 10 3 MGA D14 SN1 MGA D16 SN1...
Страница 32: ...R410A Mini Split Chiller 50Hz MCAC ATSM 2014 01 32 16 2 MGA D12 N1 Matched water pump box CE SBX N1 01A...
Страница 34: ...R410A Mini Split Chiller 50Hz MCAC ATSM 2014 01 34 16 3 MGA D14 SN1 Matched water pump box CE SBX SN1 01...
Страница 36: ...R410A Mini Split Chiller 50Hz MCAC ATSM 2014 01 36 16 4 MGA D16 SN1 Matched water pump box CE SBX SN1 01A...