MCAC-UTSM-2014-01
R410A Mini Split Chiller 50Hz
59
Electrical panel layout
No
Name
No
Name
No
Name
1
Power control board
4
Terminal board
7
Transformer
2
Fan capacitor
5
Emergency switch
3
Compressor capacitor
6
Compressor contactor
18.6.3
Outdoor unit wiring specifications
Model
Name
Quantity
Specifications
(for reference)
Notes
(purchased by customers)
10.5/12kW
Overall power core
1
RVV-300/500 3×6.0mm
2
For outdoor unit
14/16kW
Overall power core
1
RVV-450/750 5×4.0 mm
2
For outdoor unit
10.5/12/14/16kW
Water-flow controlling wire
1
AWG24(7-core shielding wire)
Between outdoor unit and
water pump box
Temp. Sensor signal wire
(shielding wire)
1
RVV-300/500 3×1.0 mm
2
Between outdoor unit and
auxiliary heater
Water pump power core
1
RVV-300/500 3×1.0 mm
2
Between outdoor unit and
water pump box
Auxiliary heater controlling
wire
1
RVV-300/500 3×1.0 mm
2
Between outdoor unit and
auxiliary heater
Controlling wire for
Central & wired controller
1
RVVP-300/300 2×0.5 mm
2
(2-core shielding wire)
Between outdoor unit and
central& wired controller
shorter than 120m.
18.7 Auxiliary electric heater installation
Содержание MGA-D10/N1
Страница 13: ...MCAC ATSM 2014 01 R410A Mini Split Chiller 50Hz 13 8 Service Space...
Страница 15: ...MCAC ATSM 2014 01 R410A Mini Split Chiller 50Hz 15 10 Wiring Diagrams 10 1 MGA D10 N1...
Страница 16: ...R410A Mini Split Chiller 50Hz MCAC ATSM 2014 01 16 10 2 MGA D12 N1 10 3 MGA D14 SN1 MGA D16 SN1...
Страница 32: ...R410A Mini Split Chiller 50Hz MCAC ATSM 2014 01 32 16 2 MGA D12 N1 Matched water pump box CE SBX N1 01A...
Страница 34: ...R410A Mini Split Chiller 50Hz MCAC ATSM 2014 01 34 16 3 MGA D14 SN1 Matched water pump box CE SBX SN1 01...
Страница 36: ...R410A Mini Split Chiller 50Hz MCAC ATSM 2014 01 36 16 4 MGA D16 SN1 Matched water pump box CE SBX SN1 01A...