R410A Mini Split Chiller 50Hz
MCAC-ATSM-2014-01
38
17. Troubleshooting
17.1
Troubles cause and solution
Troubles
Causes
Solution
Water pump doesn’t work.
1. Voltage is out of operation range.
Check wiring and circuit
2. Water flow in the water pump box is
abnormal
Check whether the water system is blocked with
sundries. Clean the filter and refill water.
Water pump works while
compressor does not work.
1. Open-circuit of compressor
connector
Check the cable connection.
2. Open-circuit of compressor wiring
Check the cable connection.
Temperature of chilled or hot
water abnormal.
1. Improper adjustment to water valve
Adjust the water valve.
2. Overload
Change to a bigger capacity chiller.
Compressor
can’t run
automatically after stop.
1. Heating in summer
Change the mode into cooling mode.
2. Cooling in winter
Change the mode into heating mode.
17.2
Malfunction code
Code
Malfunction
Code Malfunction
E0
Water flow test malfunction.
P0
Current protection.
E1
Power phase sequence malfunction.
P1
High pressure protection.
E2
Indoor & outdoor unit communication
checking channel is abnormal.
P2
Low pressure protection.
E3
Inlet temperature sensor checking
channel is abnormal.
P3
Discharge temperature protection.
E4
Outdoor ambient temperature sensor
checking channel is abnormal.
P4
Inlet
–outlet water temperature difference protection.
E5
Outlet water temperature sensor checking
channel is abnormal.
P5
Condenser high temperature protection.
E6
Condenser temperature sensor checking
channel is abnormal.
P6
Plate heat exchanger low temperature protection.
E7
Plate heat exchanger temperature sensor
1 checking channel is abnormal.
Pb
System anti-freezing protection.
E8
Plate heat exchanger temperature sensor
2 checking channel is abnormal.
P8
Inlet temperature protection (three times in one hour and
system should be powered on again).The wired controller
displays P4 when spot check.
E9
Digital scroll compressor discharge
temperature sensor is abnormal
(thermostat display E4).
Содержание MGA-D10/N1
Страница 13: ...MCAC ATSM 2014 01 R410A Mini Split Chiller 50Hz 13 8 Service Space...
Страница 15: ...MCAC ATSM 2014 01 R410A Mini Split Chiller 50Hz 15 10 Wiring Diagrams 10 1 MGA D10 N1...
Страница 16: ...R410A Mini Split Chiller 50Hz MCAC ATSM 2014 01 16 10 2 MGA D12 N1 10 3 MGA D14 SN1 MGA D16 SN1...
Страница 32: ...R410A Mini Split Chiller 50Hz MCAC ATSM 2014 01 32 16 2 MGA D12 N1 Matched water pump box CE SBX N1 01A...
Страница 34: ...R410A Mini Split Chiller 50Hz MCAC ATSM 2014 01 34 16 3 MGA D14 SN1 Matched water pump box CE SBX SN1 01...
Страница 36: ...R410A Mini Split Chiller 50Hz MCAC ATSM 2014 01 36 16 4 MGA D16 SN1 Matched water pump box CE SBX SN1 01A...