R410A Tropical Split Type Technical Manual
Troubleshooting
Floor-standing Type
89
11.4 P2 malfunction
LED indicate P2
Under cooling mode, T2 is on low
temperature protection
Judge 1: Check whether the evaporator temperature
sensor T2 is break off.
Connects it well.
Yes
No
Judge 2: Whether the evaporator temperature sensor
is malfunction.
Validate: Check whether the resistance of the
temperature sensor is correct according to Annex 1.
Replace the temperature sensor
No
Yes
Judge 3: Check whether the outdoor ambient
temperature is too low (less than 17
℃
)
Stop the unit.
Yes
No
Replace indoor PCB
Содержание MFA-76CRN1
Страница 34: ...34...
Страница 36: ...Static Pressure Tropical Split Type Technical Manual Duct Type 36 MTA 150 H CRN1 MHB 76 H CRN1 MHB 96 H CRN1...
Страница 74: ...74...
Страница 79: ...R410A Tropical Split Type Technical Manual Exploded View Floor standing Type 79 10 2 MFA 76HRN1...
Страница 81: ...R410A Tropical Split Type Technical Manual Exploded View Floor standing Type 81 10 3 MFA 96CRN1...
Страница 83: ...R410A Tropical Split Type Technical Manual Exploded View Floor standing Type 83 10 4 MFA 96HRN1...
Страница 91: ......
Страница 100: ...96...
Страница 104: ...Exploded View R410A Tropical Split Type Technical Manual 104 8 Exploded View 8 1 MOV 76CN1 C...
Страница 106: ...Exploded View R410A Tropical Split Type Technical Manual 106 8 2 MOV 76HN1 C...
Страница 108: ...Exploded View R410A Tropical Split Type Technical Manual 108 8 3 MOV 96CN1 C...
Страница 110: ...Exploded View R410A Tropical Split Type Technical Manual 110 8 4 MOV 96HN1 C...
Страница 112: ...Exploded View R410A Tropical Split Type Technical Manual 112 8 5 MOV 120CN1 C...
Страница 114: ...Exploded View R410A Tropical Split Type Technical Manual 114 8 6 MOV 120HN1 C...
Страница 164: ...Central Control Monitor Optional R410A Tropical Split Type Technical Manual Control 164 Liquid Crystal Display...