R410A
Tropical Split Type Technical Manual
Installation of Outdoor Units
Installation
127
3. Installation of Outdoor Units
3.1 Important: Construction Checkpoints
1). Installation
Check the model and name to avoid mistaken installation.
2). Refrigerant pipe
•
The refrigerant pipes must have the specified diameter.
•
Nitrogen of a certain pressure must be filled into the refrigerant pipe before welding.
•
The refrigerant pipe must undergo heat insulation treatment.
•
After the refrigerant pipe is installed completely, the indoor unit cannot be powered on before performing
the airtight test and creating a vacuum.
3). Pressure test
The refrigerant pipe must undergo the airtight test [with 2.94MPa (30kgf/cm
2
G) nitrogen].
4). Creating a vacuum
Be sure to use the vacuum pump to create a vacuum of the connective pipe at both air side and liquid side
concurrently.
5). Refrigerant replenishment
•
If the pipe is longer than the reference pipe, the refrigerant replenishment quantity for each outdoor unit
should be calculated through the formula obtained according to the actual length of the pipe.
•
Record the refrigerant replenishment quantity, actual length of pipe and the height difference of the indoor &
outdoor units onto the operation confirmation table (on the electric control box) of the outdoor unit in
advance for future reference.
6). Electric wiring
•
Select the power supply capacity and wire size according to the design manual. The power wire size of the
air conditioner should be greater than that of ordinary motors.
•
In order to prevent disoperation of the air conditioner, do not interleave or entwine the power cable
(380~415V/3N/50Hz) with the connection wires (low-voltage wires) of the indoor/outdoor unit.
•
Power on the indoor unit after performing the airtight test and making a vacuum.
7). Trial run
Perform the trial run only after the outdoor unit has been powered on for over 12 hours.
Содержание MFA-76CRN1
Страница 34: ...34...
Страница 36: ...Static Pressure Tropical Split Type Technical Manual Duct Type 36 MTA 150 H CRN1 MHB 76 H CRN1 MHB 96 H CRN1...
Страница 74: ...74...
Страница 79: ...R410A Tropical Split Type Technical Manual Exploded View Floor standing Type 79 10 2 MFA 76HRN1...
Страница 81: ...R410A Tropical Split Type Technical Manual Exploded View Floor standing Type 81 10 3 MFA 96CRN1...
Страница 83: ...R410A Tropical Split Type Technical Manual Exploded View Floor standing Type 83 10 4 MFA 96HRN1...
Страница 91: ......
Страница 100: ...96...
Страница 104: ...Exploded View R410A Tropical Split Type Technical Manual 104 8 Exploded View 8 1 MOV 76CN1 C...
Страница 106: ...Exploded View R410A Tropical Split Type Technical Manual 106 8 2 MOV 76HN1 C...
Страница 108: ...Exploded View R410A Tropical Split Type Technical Manual 108 8 3 MOV 96CN1 C...
Страница 110: ...Exploded View R410A Tropical Split Type Technical Manual 110 8 4 MOV 96HN1 C...
Страница 112: ...Exploded View R410A Tropical Split Type Technical Manual 112 8 5 MOV 120CN1 C...
Страница 114: ...Exploded View R410A Tropical Split Type Technical Manual 114 8 6 MOV 120HN1 C...
Страница 164: ...Central Control Monitor Optional R410A Tropical Split Type Technical Manual Control 164 Liquid Crystal Display...