Troubleshooting
Outdoor Units
117
Malfunctions:
About the Fault of T3A or T3B, High pressure protection, low pressure protection.
Please refer to the following:
Fault of T3A or T3B
Judge 1: Whether the sensor is break
off.
Connects it well.
Yes
Judge 2: Whether the sensor is
malfunction.
Validate: Short-connect the outdoor
ambient temperature sensor, check
whether it can run normally
Replace it.
Yes
No
No
Judge 3: PCB is malfunction
Replace PCB
Содержание MFA-76CRN1
Страница 34: ...34...
Страница 36: ...Static Pressure Tropical Split Type Technical Manual Duct Type 36 MTA 150 H CRN1 MHB 76 H CRN1 MHB 96 H CRN1...
Страница 74: ...74...
Страница 79: ...R410A Tropical Split Type Technical Manual Exploded View Floor standing Type 79 10 2 MFA 76HRN1...
Страница 81: ...R410A Tropical Split Type Technical Manual Exploded View Floor standing Type 81 10 3 MFA 96CRN1...
Страница 83: ...R410A Tropical Split Type Technical Manual Exploded View Floor standing Type 83 10 4 MFA 96HRN1...
Страница 91: ......
Страница 100: ...96...
Страница 104: ...Exploded View R410A Tropical Split Type Technical Manual 104 8 Exploded View 8 1 MOV 76CN1 C...
Страница 106: ...Exploded View R410A Tropical Split Type Technical Manual 106 8 2 MOV 76HN1 C...
Страница 108: ...Exploded View R410A Tropical Split Type Technical Manual 108 8 3 MOV 96CN1 C...
Страница 110: ...Exploded View R410A Tropical Split Type Technical Manual 110 8 4 MOV 96HN1 C...
Страница 112: ...Exploded View R410A Tropical Split Type Technical Manual 112 8 5 MOV 120CN1 C...
Страница 114: ...Exploded View R410A Tropical Split Type Technical Manual 114 8 6 MOV 120HN1 C...
Страница 164: ...Central Control Monitor Optional R410A Tropical Split Type Technical Manual Control 164 Liquid Crystal Display...