R410A
Tropical Split Type Technical Manual
Installation of Connective Pipe
Installation
143
6. Installation of Drain Pipe
6.1 Install the drain pipe of the indoor unit
•
In order to prevent drain overflow, install a drainage controller at place 1 of the drain pipe. (The drainage
controller is designed to smoothen the drainage when the static pressure outside the unit is high, especially
at the air inlet, in addition to remove stink through the drain pipe.)
•
The drain of water is natural. In the construction, the external pipe of the outdoor unit slants downward at a
gradient of 1/50~1/100.
•
The number of bends and folds of the drain pipe should not exceed 2. Try to avoid bends in order to prevent
trash accumulation.
•
In the construction, do not drop trash into the drip tray or drain pipe of the indoor unit.
•
Upon completion of installing the drain pipe, remove the inspection panel. Put water into the drip tray to
check whether the water can be drained levelly and steadily.
Checking panel
Main drain pipe
Drain pipe
Checking panel
o
v
e
r
1
0
0
m
m
o
v
e
r
5
0
m
m
Bush
(Checking orifice)
Bush
(Checking orifice)
Fig-34
NOTE:
Drain pipe trash gains easily at the drainage controller. Be sure to install a stopper and a structure that cleans up trash easily.
6.2. Trial draining of the drain pipe
Open the side panels of the indoor unit, fill water inward, and check whether the water can be drained smoothly.
Check water leak at the joint.
6.3. Heat insulation of drain pipe
After making sure that the water drains smoothly and no water is leaked, use adiabatic wool bushes to
preserve heat of the drain pipe. Otherwise, condensate will occur.
Содержание MFA-76CRN1
Страница 34: ...34...
Страница 36: ...Static Pressure Tropical Split Type Technical Manual Duct Type 36 MTA 150 H CRN1 MHB 76 H CRN1 MHB 96 H CRN1...
Страница 74: ...74...
Страница 79: ...R410A Tropical Split Type Technical Manual Exploded View Floor standing Type 79 10 2 MFA 76HRN1...
Страница 81: ...R410A Tropical Split Type Technical Manual Exploded View Floor standing Type 81 10 3 MFA 96CRN1...
Страница 83: ...R410A Tropical Split Type Technical Manual Exploded View Floor standing Type 83 10 4 MFA 96HRN1...
Страница 91: ......
Страница 100: ...96...
Страница 104: ...Exploded View R410A Tropical Split Type Technical Manual 104 8 Exploded View 8 1 MOV 76CN1 C...
Страница 106: ...Exploded View R410A Tropical Split Type Technical Manual 106 8 2 MOV 76HN1 C...
Страница 108: ...Exploded View R410A Tropical Split Type Technical Manual 108 8 3 MOV 96CN1 C...
Страница 110: ...Exploded View R410A Tropical Split Type Technical Manual 110 8 4 MOV 96HN1 C...
Страница 112: ...Exploded View R410A Tropical Split Type Technical Manual 112 8 5 MOV 120CN1 C...
Страница 114: ...Exploded View R410A Tropical Split Type Technical Manual 114 8 6 MOV 120HN1 C...
Страница 164: ...Central Control Monitor Optional R410A Tropical Split Type Technical Manual Control 164 Liquid Crystal Display...