Flooded type water cooled screw chiller (MIC)
MCAC-CTSM-2018-1
36
Checking or changing manufacturer parameters step:
①
Press one or more Esc to switch to the standard display interface;
②
Press Prg: Display interface input password;
③
Press ENTER input manufacturer password, starting from the rightmost digit, input a digit for each
confirm with ENTER;
④
If the password is correct, the following parameter type list will be displayed:
- Configuration parameters
- Sensor parameters
- Control parameters
- The special parameters
- Alert configuration parameters
- Valve parameters
Control parameter settings
13/13
DC power supply mode
1
Drive hardware configuration
3/13
Type of probe S1
User-defined
Unit type
Fin coil evaporator air-conditioner
Drive hardware configuration
4/13
Type of probe S1
NTC Carel
Auxiliary control type
Disabled
Drive hardware configuration
5/13
Type of probe S3
Unused
Relay configuration
Generate alarms
Drive hardware configuration
6/13
Type of probe S4
Unused
DI1 configuration
Start/stop SH control
Drive hardware configuration
7/13
Language
Chinese
DI2 configuration
Disabled
Control parameter settings
8/13
Overheat degree
6.0K
Valve opening upon start
50%
Pre-positioning duration
30s
Control parameter settings
9/13
Hot air by-pass temperature
---
Hot air by-pass temperature
---
EPR back pressure
---
Control parameter settings
10/13
Low SH
2.0K
LOP
-50°C
MOP
50°C
Control parameter settings
11/13
Enable manual valve positioning
0
Manually set the valve position 0stp
Control parameter settings
12/13
HiTcond threshold
80.0°C
Constant temperature
adjustment point
0°C
Constant temperature
adjustment variance
0.1K