MCAC-CTSM-2018-1
Flooded type water cooled screw chiller (MIC)
35
Running display status display all status
c. Controller parameter checking and changing.
Checking or changing repair parameters step:
①
Press one or more Esc to switch to the standard display interface;
②
Press Prg: Display the interface input password;
③
Press ENTER input repair level password: 22, starting from the rightmost digit, each input a digital and
confirm with ENTER;
④
If the password is correct, the first parameter that can be modified: Network address;
⑤
Press UP/DOWN to select parameters to set up;
⑥
Press ENTER to move to the parameter value;
⑦
Press UP/DOWN to modify the parameter value;
⑧
Press ENTER to save the new parameter values;
⑨
Repeat the above 5, 6, 7, 8 step change other parameters;
⑩
Press Esc to exit the repair parameters modify the program.
The following shows the detailed settings: 13 pages
Drive hardware configuration
1/13
Network address 198
Drive hardware configuration
2/13
Refrigerant type
R134a
Valve type
Danfoss ETS 250
Press
Press
Esc
button