Notions on refrigerant piping connection
6.1.4 Connect the pipes
When connecting the coolant pipes, be careful not to use
excessive torque or perform other operations that may
damage them. First connect the low pressure pipe and
then the high pressure pipe.
l
WARNING
When bending the connection pipes of the
refrigerant piping, observe a minimum radius
of 10 cm. See “Fig. 19”.
Radius > 10 cm
Fig. 19
TORQUES
Outer diameter of the pipe
(mm)
Tightening torque
(N•m)
Ø 6,35 (Ø 1/4”)
14,2 - 17,2
Ø 9,52 (Ø 3/8”)
32,7 - 39,9
Ø 12,7 (Ø 1/2”)
49,5 - 60,3
Ø 15,9 (Ø 5/8”)
61,8 - 75,4
m
CAUTION
DON'T USE EXCESSIVE TORQUE.
Excessive force can cause the nut to break or
damage the refrigerant piping. Do not exceed
the torque values shown in the table.
6.2 Connecting the pipes to the indoor unit
1
Align the centre of the two pipes to be connected.
A
Indoor unit
piping
Flared nut
Pipe
Fig. 20
2
Apply a little lubricating oil only to the inner surface of
the countersink (A).
3
Screw the flared nut by hand as far as possible.
4
Then insert a key on the nut.
5
Holding the nut firmly on the unit piping, use a torque
wrench to tighten the countersunk nut according to
the torque values in table “TORQUES”. Slightly loosen
the flared nut, then tighten it again.
Fig. 21
Содержание CLIVET SINGLESplit STELVIO 27M
Страница 30: ...30 Allegati 8 ALLEGATI 8 1 Schemi elettrici unit esterna 27M 35M SERIE GRANDEZZA MH2 Y 27M 35M...
Страница 31: ...31 Allegati...
Страница 33: ...OUTDOOR UNIT SINGLESplit STELVIO MH2 Y series from 27M to 35M MANUAL FOR INSTALLATION USE AND MAINTENANCE...
Страница 62: ...30 Attachments 8 ATTACHMENTS 8 1 Outdoor Unit Wiring Diagrams 27M 35M SERIES SIZE MH2 Y 27M 35M...
Страница 63: ...31 Attachments...
Страница 65: ...UNIT EXTERNE MONOSplit STELVIO S rie MH2 Y de 27M 35M MANUEL POUR L INSTALLATION L UTILISATION ET L ENTRETIEN...
Страница 94: ...30 Pi ces jointes 8 PI CES JOINTES 8 1 Sch mas lectriques de l unit externe 27M 35M S RIE TAILLE MH2 Y 27M 35M...
Страница 95: ...31 Pi ces jointes...
Страница 97: ...D AUSSENEINHEIT MONOSplit STELVIO Baureihe MH2 Y von 27M bis 35M HANDBUCH F R INSTALLATION GEBRAUCH UND WARTUNG...
Страница 126: ...30 Anlagen 8 ANLAGEN 8 1 Schaltpl ne f r Au eneinheit 27M 35M BAUREIHE GR SSE MH2 Y 27M 35M...
Страница 127: ...31 Anlagen...