Aqua Tempo Power Series (with LAK) air cooled scroll chiller unit (50Hz) MCAC-ATSM-2013-11
162
NOTE:
In operating, press the key "CANCEL", to turn back to the previous step or the normal display interface.
1.Before power failure of the heating water system or wired controller, the wired controller memorizes the
status of the unit automatically, and sets the water temperature value except timing on/off function. After
being powered on, the wired controller will send the relevant signals to the heating water system according
to memorized status before power failure, in order to ensure that the unit can run in the originally set status
after restoration of the power supply.
2. In the normal status, the background light is off. Press any key can only turn on the background light .
3. In order to protect the equipment, it is not allowed to change the running mode quickly or frequently. It
should operate the wired controller to start up the unit after 3 minutes later or all units are shutdown.
4. The wired controller and the outdoor unit must connect with the same power supply, powered up and
powered off simultaneously. It is not allowed to cut off the power supply separately.
5. When several wired controllers are parallel co
nnected, the timing message can’t communicating in these
wired controllers, and the timing will work separately. In order not to confuse, we suggest set the timing
message on one wired controller for the reason of indoor unit performance is compliance with the sequence
of setting time.
6.During changing or installing the battery, pay attention to the “+”,“-” poles of the battery and install it
correctly, or will damage the control panel or battery, even worse will put lives at risk.
Note
:
The gateway will be used with wired controller together
(
The LONWORKS gateway can be use
independently without wired controller
)
, as below:
Wired controller
LONWORKS
gateway
BACnet
gateway
Network control
software
MODBUS gateway
KJR-120A/MBTE
√
√
√
×
KJRM-120D/BMK-E
√
×
×
√
Содержание Aqua Tempo Super Series
Страница 37: ...Aqua Tempo Power Series with LAK air cooled scroll chiller unit 50Hz MCAC ATSM 2013 11 36 130kW module...
Страница 38: ...MCAC ATSM 2013 11 Aqua Tempo Power Series with LAK air cooled scroll chiller unit 50Hz 37 200kW module...
Страница 39: ...Aqua Tempo Power Series with LAK air cooled scroll chiller unit 50Hz MCAC ATSM 2013 11 38 250kW module...
Страница 45: ...Aqua Tempo Power Series with LAK air cooled scroll chiller unit 50Hz MCAC ATSM 2013 11 44 200kW module...
Страница 48: ......
Страница 62: ...MCAC ATSM 2013 11 Aqua Tempo Power Series with LAK air cooled scroll chiller unit 50Hz 61...
Страница 69: ...Aqua Tempo Power Series with LAK air cooled scroll chiller unit 50Hz MCAC ATSM 2013 11 68...
Страница 71: ...Aqua Tempo Power Series with LAK air cooled scroll chiller unit 50Hz MCAC ATSM 2013 11 70 MGBL D65W RN1...
Страница 72: ...MCAC ATSM 2013 11 Aqua Tempo Power Series with LAK air cooled scroll chiller unit 50Hz 71...
Страница 74: ...MCAC ATSM 2013 11 Aqua Tempo Power Series with LAK air cooled scroll chiller unit 50Hz 73 10 4 MGBL F130W RN1...
Страница 77: ...Aqua Tempo Power Series with LAK air cooled scroll chiller unit 50Hz MCAC ATSM 2013 11 76 10 5 MGBL F200W RN1...
Страница 80: ...MCAC ATSM 2013 11 Aqua Tempo Power Series with LAK air cooled scroll chiller unit 50Hz 79 10 6 MGBL F250W RN1...
Страница 100: ...MCAC ATSM 2013 11 Aqua Tempo Power Series with LAK air cooled scroll chiller unit 50Hz 99 55 60 65kW module 130kW module...