Aqua Tempo Power Series (with LAK) air cooled scroll chiller unit (50Hz) MCAC-ATSM-2013-11
136
1) If faults occur between the wired controller and the main unit module, all modules will be shut down.
2) If faults occur between the main unit and subordinate units, the subordinate unit module suffering communication fault will
be shut down. Less units will be detected by the wired controller, which may display EA, and in the meanwhile, the indicator
lamp of the wired controller will flash, restart 3 minutes later after malfunction be removed.
12
High-pressure protection of the system A and discharge temperature switch protection (Protection code P0).
High-pressure protection of the system B and discharge temperature switch protection (Protection code P2).
Low-pressure protection of the system A (Protection code P1).
Low-pressure protection of the system B (Protection code P3).
Constant speed compressor: connection of discharge temperature switch and high-pressure switch of the system in series.
13
Inlet water temperature sensor (Fault code EF).
14
Shell and tube low-temperature ant-freezing sensor (Fault code Eb).
15
Water flow detection (Fault code of the main unit E9) is only valid for the main unit but invalid for subordinate units.
1) Main unit: if abnormal water flow occurs , the main unit board and the wired controller will display fault code E9.
2) Subordinate unit: (Water flow detection will not be done).
16
Power phase detection(Fault code E8).
17
Electronic expansion valve of the system B.
18
Electronic expansion valve of the system A.
Electronic expansion valve is used to control refrigerant flow under different operating modes and different loads.
19
Auxiliary electric heater.
Attention: the control port value of auxiliary electric heater actually detected is ON/OFF but not 220-240V control power
supply, so special attention should be paid when installing the auxiliary electric heater.
Attention!
Under heating mode, when the main unit board detects total water outlet temperature to be lower than 45
℃
, the switch will be
closed, and the auxiliary electric heater will begin to work; when the total water outlet temperature is higher than 50
℃
, the
switch will be opened, and the auxiliary electric heater will stop working.
20
PUMP.
Attention: the control port value of the pump actually detected is ON/OFF but not 220-240V control power supply, so special
attention should be paid when installing the pump.
1) After receiving start-up instruction, the pump will be started up instantly, and will maintain start-up state always in the
process of operation.
2) In case of refrigerating or heating shutdown, the pump will be shut down 2 minutes after all modules stop operating.
3) In case of shutdown under the pump mode, the pump can be directly shut down.
21
One compressor of the system B(B1).
Neutral wire.
Four-way valve of the system B.
Neutral wire.
22
Numerical code tube.
1) In case of stand-by, the address of the module is displayed.
2) In case of normal operation, 10. is displayed (10 is followed by dot).
3) In case of fault or protection, fault code or protection code is displayed.
23
One compressor of the system A(A1).
Neutral wire.
Four-way valve of the system A.
Neutral wire.
24
Outdoor fan A, controlled by T4.
25
Outdoor fan B, controlled by T4.
26
PWM pressure relieve valve control(for digital compressor).
Содержание Aqua Tempo Super Series
Страница 37: ...Aqua Tempo Power Series with LAK air cooled scroll chiller unit 50Hz MCAC ATSM 2013 11 36 130kW module...
Страница 38: ...MCAC ATSM 2013 11 Aqua Tempo Power Series with LAK air cooled scroll chiller unit 50Hz 37 200kW module...
Страница 39: ...Aqua Tempo Power Series with LAK air cooled scroll chiller unit 50Hz MCAC ATSM 2013 11 38 250kW module...
Страница 45: ...Aqua Tempo Power Series with LAK air cooled scroll chiller unit 50Hz MCAC ATSM 2013 11 44 200kW module...
Страница 48: ......
Страница 62: ...MCAC ATSM 2013 11 Aqua Tempo Power Series with LAK air cooled scroll chiller unit 50Hz 61...
Страница 69: ...Aqua Tempo Power Series with LAK air cooled scroll chiller unit 50Hz MCAC ATSM 2013 11 68...
Страница 71: ...Aqua Tempo Power Series with LAK air cooled scroll chiller unit 50Hz MCAC ATSM 2013 11 70 MGBL D65W RN1...
Страница 72: ...MCAC ATSM 2013 11 Aqua Tempo Power Series with LAK air cooled scroll chiller unit 50Hz 71...
Страница 74: ...MCAC ATSM 2013 11 Aqua Tempo Power Series with LAK air cooled scroll chiller unit 50Hz 73 10 4 MGBL F130W RN1...
Страница 77: ...Aqua Tempo Power Series with LAK air cooled scroll chiller unit 50Hz MCAC ATSM 2013 11 76 10 5 MGBL F200W RN1...
Страница 80: ...MCAC ATSM 2013 11 Aqua Tempo Power Series with LAK air cooled scroll chiller unit 50Hz 79 10 6 MGBL F250W RN1...
Страница 100: ...MCAC ATSM 2013 11 Aqua Tempo Power Series with LAK air cooled scroll chiller unit 50Hz 99 55 60 65kW module 130kW module...